Descargar Imprimir esta página

Program Scenes 1 Through 16 (Setup Mode) - Lutron GRAFIK Eye 4000 Serie Manual De Instalación

Ocultar thumbs Ver también para GRAFIK Eye 4000 Serie:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 29

Program Scenes 1 through 16 (Setup Mode)

You can program any scene using setup mode. If your lighting system requires more than 4 scenes, scenes 5 
through 16 must be programmed using setup mode.
NOTE: To program scenes 1 through 4 using Sd save mode, refer to page 18.
Select flashing Sc/1
2
ZONE 1
ZONE 2
4
Program lighting 
or shade scene 
settings for each 
zone
ZONE 5
ZONE 6
4
To set unaffected zone, 
press ZONE 
 twice 
6
and then hold until mid-
dle three LEDs light
20     GRAFIK Eye
 4000 Series Control Unit Installer's Guide 
®
5
Set scene's  
fade-in time
FADE
TEMPORARY
3
ZONES
Select scene
M S
MASTER
FADE
TEMPORARY
ZONES
M S
MASTER
To program scenes using setup mode:
1. Enter setup mode. Press and hold the SCENE 1 
and OFF buttons for about three seconds until the 
scene LEDs start cycling.
2. Select Sc (scene setup) by pressing the 
FADE 5 button twice. Sc and 1 (scene 1) will 
alternately flash in the FADE window.
3. Select scene. Press the MASTER 5 or 6 
button to select the number of the scene to be 
1
6
,
programmed (1 through 15; 0 is the OFF scene).
4. Program scene settings for each zone.
Enter (exit) 
setup mode
  For lighting zones, press the ZONE 5 or 6 
button to set the zone intensity. (GRX-3500 units 
will display exact percentage light output; press 
again to adjust light levels in 1% increments.)
  For AC shade zones, press the ZONE 5 or 6 
button until the ZONE LEDs match the right shade 
position for this scene. See the illustration on page 
18.
  For Sivoia QED shade zones, press the 
ZONE 5 or 6 button until the ZONE LEDs match 
the right shade position for this scene. See the 
illustration on page 18.
For unaffected zones, press and hold the 
ZONE 6 button until all its LEDs go out and the 
middle three LEDs light (this may take up to 10 
seconds). This zone's settings will not be affected 
when this scene is selected.
To reprogram an unaffected zone as affected,
follow the steps above. Then press the ZONE 5 
button for about three seconds until the middle 
three ZONE LEDs are no longer lit. Program the 
zone's settings.
5. Set the scene's fade-in time. Press and hold 
the TEMPORARY ZONES button. The current fade-
in time will be displayed. Adjust using the FADE 5
or 6 button while still holding the TEMPORARY 
ZONES button. (Fade time does not apply to shade 
zones.)
6. Exit setup mode. Press and hold the SCENE 1 
and OFF buttons until the LEDs stop cycling.