Section 2:
Installing a GRAFIK Eye
This section explains how to install a GRAFIK Eye control unit and make sure it is properly operating all connected 
loads.

Step 1: Turn the Power OFF

CAUTION! Before continuing with the installation, make sure the power is turned OFF at the panel supplying 
power to the control unit. Do not perform any wiring with the power ON.

Step 2: Control Wiring

Panel
Wallstation
GRAFIK  
Panel
Eye
Wallstation
Control 
interface
Correct: Daisy chain OK
Control Link Specifications
Total length of control link may be no more than 2000 feet (610 
m). This distance is based on proper shielding on the twisted 
shielded pair, and on #12 AWG (2.5 mm
terminal 1 and terminal 2 of the control link. If unapproved cable 
or smaller wire is used, this limit is affected:
Terminal 1 & 2 Wire Sizes
#12 AWG (2.5 mm
) 
2
#14 AWG (1.5 mm
) 
2
#16 AWG (1.0 mm
) 
2
#18 AWG (1.0 mm
) 
2
Total number of control unit addresses = 8 maximum
Note:   G RX-4116/4516 has 2 addresses 
GRX-4124/4524 has 3 addresses
Total number of wallstation or control interface addresses = 16 maximum
Total number of shade controller addresses = 8 maximum
Notes:
•  Make wire connections inside the wallbox and panel or in a junction box (by others) within 8 ft. (2.4 m) of the 
terminal.
•  All control wiring is PELV (Class 2: USA). Do not place any of these wires in with line voltage (mains voltage) wiring.
•  The order of controls within the control wiring is not important.
PELV (Class 2: USA) Notice
Wallstation circuits are classified as Class 2 circuits (U.S.A.) and PELV circuits (IEC). Unless otherwise specified, 
the voltages do not exceed 24 V
Electrical Code (NEC
®
410, BS7671:1992 and other equivalent standards. When installing and wiring to these wallstations, follow all 
applicable national and/or local wiring regulations. External circuits connected to input, output, RS232, DMX512, 
and other communication terminals of wallstations, must be supplied from a listed Class 2 source or comply with 
the requirements for PELV circuits, as applicable in your country.
4     GRAFIK Eye
 4000 Series Control Unit Installer's Guide 
®
GRAFIK  
Eye
Control 
interface
GRAFIK  
Eye
To other panels, GRAFIK Eye 
control units, wallstations, or 
control interfaces.
) wire on the wires to 
2
Max. Control Link Length
2000 ft. (610 m) 
1400 ft. (425 m) 
900 ft. (275 m) 
600 ft. (180 m)
. As Class 2 circuits, they comply with the requirements of NFPA 70. National 
). As PELV circuits, they comply with the requirements of IEC 60364-4-41, VDE 0100 Part 
Control Unit
®
Incorrect: Branch or home run not acceptable
2000 ft (610 m) maximum
R