Descargar Imprimir esta página

Factory Presets; System Communications And Capacities - Lutron GRAFIK Eye 4000 Serie Manual De Instalación

Ocultar thumbs Ver también para GRAFIK Eye 4000 Serie:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 29

Factory Presets

Lutron ships each control unit with the following factory presets. For slider models, see the Addendum included 
with those control units.
Setting
Address 
Load type 
Scene 1 
Scene 2 
Scene 3 
Scene 4 
Scenes 5-16 
OFF 
Fade times 
Fade time from OFF  4 seconds to any scene (not adjustable)
Save mode 
Note: Scene fade time affects lights but not shades; shades move immediately to their programmed level.
Accessories
Depending on the size and requirements of the lighting system, control units can be configured to work with a 
variety of optional accessories, including:
•  Low-voltage wallstations. Wallstations, shade controllers, infrared (IR) sensors and receivers, and door-jamb 
controls.
•  Control interfaces. Contact closure devices, RS232 and Ethernet digital communications, and programming 
interface with astronomic timeclock (programmed using GRAFIK Eye Liaison
For part numbers and additional information on GRAFIK Eye 4000 Series accessories, visit www.lutron.com.

System Communications and Capacities

PELV (Class 2: USA) cable can be used to connect GRAFIK Eye 4000 control units, wallstations, and other 
accessories. You can link up to 8 control units to control up to 64 zones, and add up to 16 wallstations and 8 
shade controllers (SG-SVC) for a total of 32 control points. 16-zone control units count as 2 addresses and 2 
control units, and 24-zone control units count as 3 addresses and 3 control units. Note that wallstations control 
scenes (which can include light and shade settings); shade controllers control only shades. 16- and 24-zone 
control units and slider models do not have shade zones.
PELV (Class 2: USA) Cables
If your lighting system uses wallstations and/or multiple control units, PELV (Class 2: USA) wiring is needed to 
supply power and carry communications between the control units and the wallstations. PELV (Class 2: USA) wiring 
is also needed to connect other accessories.
Use properly certified PELV (Class 2: USA) cable. Each twisted pair in the PELV (Class 2: USA) wiring link should 
consist of two stranded conductors and a drain/shield wire.
•  The pair of #12 AWG (2.5 mm
•  The pair of #22 AWG (1.0 mm
Note:   L utron offers a one-cable, low-voltage solution: P/N GRX-CBL-46L (non-plenum) or GRX-PCBL-46L (plenum). 
Check availability and applicable electrical codes in your area.
In countries that abide by the IEC regulations, PELV is commonly referred to as Protective Extra-Low Voltage. 
A PELV circuit is a grounded circuit in which the voltage cannot exceed 50 V  or 120 V
source must be supplied by a safety isolating transformer or equivalent.
In Europe, acceptable types of cable include HAR certified cable with insulated cores enclosed in a sheath. This 
cable must bear the appropriate certification mark pertaining to national wiring rules for fixed installations. If 
certified cable with insulated cores enclosed in a sheath is used for the power cables, the PELV wiring can be any 
of the cables listed above.
R
Factory Preset
Not addressed (A-)
All zones set to incandescent
100% intensity for all zones
75% intensity for all zones
50% intensity for all zones
25% intensity for all zones
100% intensity for all zones
All zones OFF
3 seconds between all scenes; 10-second fade time to OFF
Sd (save by default)
2 
) is for the low-voltage power wiring.
2 
) is for a data link (up to 2000 ft/610 m long).
 software). 
TM
GRAFIK Eye
 4000 Series Control Unit Installer's Guide     3
®
 ripple-free. The power 

Publicidad

Solución de problemas

loading

Este manual también es adecuado para:

Grafik eye 4100Grafik eye 4500