7-1 Normal measurement of current

* Press the Function button
* Confirm the displayed unit is " mA", and the " MEM" mark is not displayed at the upper left corner of the
LCD.
* Press the lever to open the transformer jaws and close them over a single conductor.
* The measured current value is then displayed on the LCD. (Earth leakage current that flows through a
ground wire can also be measured by this method.)
7-2 Measurement of Balanced leakage current
* Press the Function button
* Confirm the displayed unit is " mA", and the " MEM" mark is not displayed in the upper left corner of
the LCD.
* Clamp onto all conductors except the earthed wire.
* The measured current value is displayed on the LCD.
Single-phase 2-wire system
In 3-wire system with neutral, clamp onto
A/Ω
and select the ACA function.
and select the ACA function.
A/Ω
all 3 wires.
Three-phase 3-wire system
In 4-wire system with neutral, clamp
onto all 4 wires.