2. Features

The 61-920 is a digital clamp-on ground resistance tester. The instrument can measure the ground resist-
ance by simply clamping around the ground conductor, ground rod or equipment ground conductor.
The 61-920 also measures leakage AC current up to 30AAC.
Wide measuring range (Auto-ranging)
Ground resistance
AC current
Noise check function senses current on the ground electrode or ground wire and displays NOISE on
the LCD display.
True RMS feature accurately measures AC current even with distorted waveforms due to harmonics.
Auto power-off feature powers the meter down automatically after 10 minutes of non-use to conserve
battery power.
Data hold feature is used to capture and hold a reading in the LCD display.
Continuity buzzer function provides an audible warning to the user when the measurement result is
10Ω or less.
Backlight feature illuminates the display for working in dimly lit areas.
Memory save feature records and displays the measurement result.
Complies with IEC61010-1: 2001 (CAT.IV 300V Pollution degree 2), IEC61010-2-032: 2002 safety
standards.
This instrument is protected by double or reinforced insulation
Max. 1200Ω
Max. 30A
Page 5
Min. resolution 0.01Ω
Min. resolution 0.1mA
.