Technical Specifications; Operating Temperature - WEG PLC300 H3 Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical Specifications

4 TECHNICAL SPECIFICATIONS
Supply:
Voltage: 24 Vdc ± 15 %.
Consumption of the PLC300 in 24 V: 250 mA.
Approximate consumption of each expansion: 30 mA.

Operating temperature

0 °C to 50 °C.
Degree of protection
IP65.
DI1 to DI10 Digital Inputs:
Bidirectional inputs.
Maximum input voltage 30 Vdc.
High level: Vin ≥ 10 V.
Low level: Vin ≤ 3 V.
Consumption in 24 V: 10 mA.
Maximum frequency DI1 to DI8: 4 kHz.
Maximum frequency DI9 and DI10: 100 kHz.
Insulation voltage: 500 V.
Delay time DI1 to DI8: 0→1: 20 µs; 1→0: 60 µs.
Delay time DI9 to DI10: 0→1: 8 µs; 1→0:32 µs.
DO1 to DO8 Digital Outputs:
PNP Outputs.
Maximum voltage in Vbb: 30 Vdc.
Maximum current of each output: 500 mA.
Delay time DO1 to DO8: 0→1: 40 us; 1→0: 125 us.
PWM DO9 Output:
Push-pull output.
Maximum voltage in Vbb: 30 Vdc.
Maximum current: 100 mA.
Maximum frequency: 300 kHz.
Note:
To use it as PWM, the maximum frequency must be 50 kHz so that the duty-cycle
is correct.
Analog Output
10-Bit Resolution.
Independent terminals for voltage and current.
Voltage output from 0 to 10 V.
Current output from 0 to 20 mA.
Maximum load 500 Ω for current output.
16 | PLC300

Publicidad

Tabla de contenido
loading

Tabla de contenido