A
II
NNEX
Schedule timer example
MARCH
MON
TUE
WED
1
G1
2
G1
3
G2
4
8
G1
9
G1
10
G2
11
15
G1
16
G1
17
G2
18
22
G1
23
H
24
H
25
29
H
30
G1
31
G2
To come to the schedule above following settings have to be made:
BX
SCHEDULE TIMER
MON : G1 THU : G1 SAT : G3
TUE : G1 FRI : G1 SUN : G3
WED : G2
BX
HD PERIOD : 01 TO 03
01 : 23/03 TO 29/03
02 : 00/00 TO 00/00
03 : 00/00 TO 00/00
All days assigned to the same group will work according to the
settings of this group.
In this example setting:
all Mondays, Tuesdays, Thursdays and Fridays will work accord-
ing to the settings in group 1 (G1),
all Wednesdays will work according to the settings in group 2
(G2),
all Saturdays and Sundays will work according to the group 3
(G3),
all holiday days will work according to the settings in the holiday
group (H).
All group settings of groups G1, G2, G3, G4 and H work similar as
following example (settings for group 1):
14.0°C
Cooling inlet setpoint 1
12.0°C
Heating inlet setpoint 1
Cooling
Heating
On
Off
6
8
Screen 1
BX
GROUP1 : 01 TO 03
1 : 06h00 ISP1 E : 12.0
2 : 06h00 ON COOL
3 : 08h00 ISP1 E : 14.0
Screen 2
BX
GROUP1 : 04 TO 06
4 : 12h00 OFF
5 : 13h00 ISP1 C : 30.0
6 : 13h00 ON HEAT
Screen 3
BX
GROUP1 : 07 TO 09
7 : 15h00 ISP1 C : 35.0
8 : 20h00 OFF
9 : 00h00 -
-
Operation manual
17
THU
FRI
SAT
SUN
G1
5
G1
6
G3
7
G1
12
G1
13
G3
14
G1
19
G1
20
G3
21
H
26
H
27
H
28
35.0°C
14.0
14.0°C
30.0°C
12 13
15
18
20
time (h)
G3
G3
G3
H
EWWQ049~064KAW1M + ECB2+3MUBW
Packaged water-cooled water chillers
D-EOMHP01008-17EU