To facilitate control and maintenance operations, install an interception valve both on the suction pipe and
on the delivery pipe.
Before installing the circulator, accurately flush the system with only water at 80°C. Then drain the system
completely to eliminate any harmful substance that may have got into circulation.
Avoid mixing additives derived from hydrocarbons and aromatic products with the circulating water. It is
recommended that the addition of antifreeze, where necessary, should not exceed 30%.
In the event of heat insulation use the special kit (if provided) and ensure that the condensate draining
holes in the motor casing are not closed or partly blocked.
In the case of maintenance, always use a set of new gaskets.
Never insulate the electronic control device.
8.2.1 Positioning of the user interface in heating and domestic hot water systems
It is possible to position the user interface with the cable facing to the left, to the right, or downwards.
ENGLISH

Figure 4: Positions of the user interface