Set-up & Commissioning
Time delay: 10 seconds to 15 minutes
Test mode
• Ensure that the sensor is in test mode.
- Set time delay to minimum setting
of 10 seconds
- Set light level to maximum
("day" setting, light level function
overridden)
• Turn power ON at the circuit breaker
(lights will turn ON). After a warm up
period of up to one minute, lights will
turn OFF if the sensor does not detect
motion.
• Walk in view of sensor, lights should
turn ON. Be still for 10 seconds and
lights should turn OFF.
night
Light level: .2 (night) to 200 (day) footcandles
Light level
The light level feature allows lighting to
remain OFF during daylight, regardless of
occupancy. Daytime operation is at 200
footcandles (factory setting). Nighttime
operation is at .2 footcandles.
Time delay
Time delay is the period of time lights
remain on after the last detection.
Adjustment ranges from 10 seconds
(factory setting) to 15 min.
After set-up and commissioning tests are
complete, adjust the time delay and light
level settings to fit the application needs.
www.steinel.net
7
day
(800) 852-4343