while the gate Is opening, It has no effect. If It Is
operated when the gate Is open, It closes. If It Is
operated while the gate Is closing, It opens the gate
again.
AUTOMATIC CLOSING FOR COMPLETE OR PEDESTRIAN OPENING
The pausing time before the automatic closing for both, complete or
pedestrian opening is set during the time programming. In both cases the
maximum pausing time available is 5 minutes . Pause time can be started
or stopped by DIP3 (ON started).
OPERATION AFTER BLACK-OUT
When mains electrical power is restored press the opening button (K,
OPEN, radio).
The gate will open. Let the gate close itself with automatic closure or wait
that the flasher stops blink first to command the closing movement. This
operation is valid to obtain the leaves position readjustment. During this
phase all safety devices are active.
S
AFETY ACCESSORIES OPERATION
PHOTOCELL 1 (COM-PHOT 1))
If DIP 6 is OFF => The gate does not open if there Is an obstacle within
the photocells range of action. During operation,
photocells work both when the gate opens (by
starting the opening movement again after half a
second time), and when It closes (by starting the
reverse movement after one second time).
If DIP 6 is ON => If there Is an obstacle within the photocells range of
action when the gate is closed and its opening Is
commanded, the gate opens (during Its opening,
photocells do not work). Photocells work only while
the gate Is closing (by starting Its reverse motion after
one second, even if they are still engaged).
STOP BUTTON
The STOP button stops the gate during any operation.
If you push it when the gate is totally open (or partly open, by using the
pedestrian command), this button temporary excludes the automatic
closing (if selected by DIP3 and DIP9). It Is than necessary to operate
another command to make the gate close again.
The automatic closing function Is enabled again with the following
operating cycle (if selected by DIP3 and DIP9).
BLINKER
N.B.: This electric board can supply power ONLY TO BLINKERS
WITH (ACG7059) BLINKING CIRCUIT, with max. 40W lamps.
PRE-BLINKING FUNCTION:
- With DIP8 on OFF => the motor, the blinker and the buzzer start at the
same time.
- With DIP 8 on ON => the blinker and the buzzer start 3 seconds
before the motor.
BUZZER (Optional)
Current as supplied for buzzer operation 200 mA 12Vdc.
The buzzer emits an intermittent sound signal during opening and
closing cycles. When safety devices are operated (alarm), the
intermittence frequency of this sound signal Increases.
WARNING LIGHT - GATE OPEN (COM-SIGNAL)
Its function Is to signal when the gate Is open, partly open or not totally
closed anyway. It turns off only when the gate Is totally closed.
This warning signal is not enabled during the programming procedures.
N.B.: If you overuse the push button panels or the lamps, the control
board logic system may be compromised, resulting into a possible
operation block.
T
ECHNICAL SPECIFICATIONS
- Moisture
- Power supply voltage
- Frequency
- Max. power consumption of the card
- Transient power mains drops
- Max. capacity of the warning light - gate open 3 W (corresponding to 1
- Max. load at blinker output
- Available current for photocells and accessories 0,4 A ±15% 24Vac
- Available current for the radio connector 200mA 12Vdc
- All the inputs must be used as clear contacts because the power supply
is generated inside (safe power) the control panel, and it has been laid
down in such a way to guarantee a double or strengthened insulation in
relation to the parts with dangerous power.
- Eventual external circuits connected to the outputs of the control board
or of the expander card must be carried out making sure that a double
or strengthened insulation is used in relation to parts with dangerous
power.
- All inputs are run by a programmed integrated circuit which does a self
check every time it starts operating.
G G
B B
< 95% without condensation
230V~ ±10% (on request
120V/60Hz)
50/60 H
60 mA
100mS
3W lamp or to 5 LEDS
with 2,2 k resistance In
series)
40W with resistive load