Change of lighting term of filter sign
According to the installation condition, the lighting term
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
1
→
2
→
3
→
4
→
5
(
• For the item code in Procedure
• For the [Set data] in Procedure
data of filter sign lighting term from the following
table.
Setup data
0000
0001
150H (At shipment from factory)
0002
2500H
0003
5000H
0004
10000H
To secure better effect of heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow to the basic operation procedure
1
→
2
→
3
→
4
→
5
(
• For the item code in Procedure
• For the set data in Procedure
data of shift value of detection temperature to be set
up from the table below.
Setup data
Detection temp shift value
0000
0001
+1°C
0002
+2°C (At shipment from factory)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
→
6
).
3
, specify [01].
4
, select the setup
Filter sign lighting term
None
→
6
).
3
, specify [06].
4
, select the setup
No shift
Group control
In a group control, a remote controller can control up
to maximum 8 units.
• For cabling procedure and cables of the individual
line (Identical refrigerant line) system, refer to
"Electric work" in this Manual.
• Cabling between indoor units in a group is performed
in the following procedure.
Connect the indoor units by connecting the remote
controller inter-unit cables from the remote controller
terminal blocks (A, B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A, B) of the other indoor unit.
(No polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
18