BTL7-A/E501-M_ _ _ _-A/B/Y/Z(8)-S32/S115/S140/KA_ _/FA_ _
Micropulse Transducer - Rod Style
6
Configuration with the Micropulse Configuration Tool (continued)
Freely configurable curve
Null and end points can be read (teach-in) or specified
with the mouse.
For position, the distance between the null point and
end point must be at least 4 mm (0.15 inch) and
100 mm/s (4 inch/s) for velocity.
The curve can be inverted or copied from the other
output.
The limits can be adjusted to the measuring range.
The error value can be set in accordance with the
limits.
Boundary conditions for two magnets
Two magnets can only be selected if the nominal length
is ≥ 90 mm.
The distance between two magnets must be ≥ 65 mm.
Locking the calibration device
The function to manually adjust the transducer with the
calibration device can be locked, making configuration only
possible with the PC software.
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► The system must be taken out of operation before
configuration.
► Transducers may only be connected to the
communication box for configuration.
► The communication box must be removed after
configuration.
www.balluff.com
english
15