Micropulse Transducer - Rod Style
9
Adjust with the calibration device (continued)
Switch the output to be adjusted (optional)
As standard, the values are adjusted at output 1
and the values at output 2 are inverted
accordingly.
From serial number 100503000xxxxx xx, it is
possible to optionally switch adjustment from
output 1 to output 2.
Initial situation:
Transducer with magnet within measuring range
Activate adjusting
► Press
for at least 4 s.
Switch the output to be adjusted
Œ
► Press
and
for at least 4 s, until one LED flashes
green.
⇒ Both LEDs will flash again once the buttons are
released.
► Continue with Set start point (see page 20).
22
english
2
> 4 s
1
2
LED legend:
LED not on
LED green
LED flashing green
LED display
Displayed values (example)
LED1 LED2 At 0 to 10 V
5.39 V
5.39 V
For output 2 or
for output 1 (changes with
each switch)
LED 1 and LED 2 flashing red-red in alternation
At 4 to 20 mA
9.15 mA
9.15 mA