3.2 Setting the DIL switches
1
DIL switch 1:
Bus node
operation mode
2
DIL switch 2:
only for operating
mode Remote I/O:
Diagnostic mode
Setting the operating mode with DIL switch 1
You can set the operating mode of the bus node with
switch element DIL 1.1 of DIL switch 1:
DIL switch 1
Festo CPX−FB38 0804NH English
1
Setting
DIL 1.1: OFF
DIL 1.2: OFF
(factory
setting)
DIL 1.1: ON
DIL 1.2: OFF
Function
Operating mode Remote I/O
All functions of the CPX terminal
are controlled directly by the
EtherCAT I/O controller or a
superordinate SPS
Remote controller
A CPX−FEC integrated in the
terminal controls all functions
2
19