Wiring the GRAFIK Eye

Power Group Wiring Example

On the QS link, there are devices that supply power and devices that consume power. Each device has a specific number of Power
Draw Units (PDUs) it either supplies or consumes. A Power Group consists of one device that supplies power and one or more
devices that consume power; each Power Group may have only one power-supplying device. Refer to the QS Link Power Draw Units
specification submittal (Lutron PN 369405) for more information concerning PDUs.
Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram. Between devices on
the QS link that supply power, connect only terminals 1, 3, and 4 (NOT terminal 2), shown by the letter B on the diagram.
Wiring can be T-tapped or daisy-chained.
LUTRON
GRAFIK Eye
QS
®
control unit
Supplies PDUs
B
(Do not connect
terminal 2: 24 V )
Energi Savr Node
TM
unit Supplies PDUs
B
(Do not connect
terminal 2: 24 V )
QS Power Supply
Control Interfaces
Supplies PDUs
Consume PDUs
B
®
QS with DALI Control Unit:
®
A
Control Interfaces
Wallstations
Consume PDUs
Consume PDUs
A
Wallstations
Consume PDUs
A
Wallstations
Consume PDUs
Quantum
panel
®
Supplies PDUs
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
Power Group 1
Power Group 2
Power Group 3
QS Sensor Module with
Occupancy Sensor
Consumes PDUs
QS with DALI Control Unit Quick Installation and Operation Guide 8
®
A
Connect all 4 terminals within a
power group:
1: Common
2: 24 V
3 and 4: Data
B
Connect only 3 terminals
between power groups:
1: Common
3 and 4: Data
Do not connect
Terminal 2: 24 V