Madas XVO/NC Serie Manual Del Usuario página 14

Electroválvula automática normalmente cerrada para gas con apertura rápida
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8.0 - RATING PLATE DATA
The user is obliged to keep the marking of the valve clearly visible: any coatings or
paintwork performed on the product that make the valve unidentifiable are not to be
attributed to the manufacturer.
The rating plate data (see example provided here) includes the following:
• Manufacturer's name/logo and address (possible distributor name/logo)
• Mod.:
= name/model of the device followed by the diameter size
• CE-51BP2537 = certification pin number
• Cl. A
= Seal strength in counterflow at 150 mbar in accordance with EN 161
• Gr. 2
= Mechanical resistance group 2 in accordance with EN 161
• EN 161
= Product reference regulation
• P.max
= Maximum pressure at which product operation is guaranteed
• IP....
= Protection rating
• 230V....
= Power supply voltage, frequency (if Vac), followed by electrical absorption
Example of electrical absorption indication: 9/3 VA indicates 9 VA at start, 3 VA at steady state
• TS
= Temperature range within which product operation is guaranteed
= Conformity with Regulation (EU) 2016/426 followed by Notified Body No.
= In compliance with ATEX followed by the protection mode
(complete protection mode indicated on coil and CPI switch)
• year
= Year of manufacture
• Lot
= product serial number (see explanation below)
• U1804
= Lot issued in year 2018 in the 4th week
• 2185
= progressive job order number for the indicated year
• 00001
= progressive number referred to the quantity of the lot
Protection mode
II
product group
3
product category
Gas: II 3G Ex mc ec nC IIC T... Gc X
G
explosive atmosphere with gas or vapours
Ex
suitable for explosive atmosphere
mc
encapsulated for zone 2
ec
increased safety
nC
sealed device for zone 2
IIC
explosion group
temperature class (T4 < 135 °C) - (T5 < 100 °C) - (T6 < 85 °C)
T...
Gc
Product Level (EPL) - equipment for use in explosive atmospheres due to the presence of gas, with an "increased"
level of protection, which is not a source of ignition during normal operation and which has some additional protective
measures to ensure that it remains an inactive source of ignition in case of events expected regularly
X
particular conditions of use (*)
Dust: II 3D Ex mc tc IIIC T...°C Dc X
D
explosive atmosphere with dust
Ex
suitable for explosive atmosphere
mc
encapsulated for zone 22
tc
protection by enclosure for zone 22
IIIC
explosion group
T...
temperature class expressed in °C
Dc
Product Level (EPL) - equipment for use in explosive atmospheres due to the presence of dust, with an "increased"
level of protection, which is not a source of ignition during normal operation and which has some additional protective
measures to ensure that it remains an inactive source of ignition in case of events expected regularly
X
particular conditions of use (*)
* see paragraph 3.2 - "Special conditions for safe use"
XVO.../NC - XVOA.../NC
Mod: XVO/NC DN 15
CE- 51BP2537 CI.A GR.2 EN 161
IP65 – 230 V/50-60 Hz 9/3 VA
year: 2018
14
Madas Technical Manual - 1|1.1X - REV. 1 of 6
P. max: 200 mbar
TS: -20+85 °C
II 3G
0051
II 3D
Lot:U1804
2185/00001
th
Jul 2020

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Xvoa/nc serie

Tabla de contenido