"B" Group: Fine-tuning Functions
Func.
Code
B001
Selection of automatic restart mode
• 00 Alarm output after trip, automatic
restart disabled
• 01 Restart at 0Hz
• 02 Resume operation after frequency
matching
• 03 Resume previous freq. after freq.
matching, then decelerate to stop and
display trip info
B002
Allowable under-voltage power failure time
B003
Retry wait time before motor restart
B004
Instantaneous power failure / under-voltage
trip alarm enable
• 00 Disable
• 02 Disable during stop and ramp to stop
B005
Number of restarts on power failure / under-
voltage trip events
• 00 Restart 16 times • 01 Always restart
B006
Phase loss detection enable
• 00 Disable – no trip on phase loss
• 01 Enable – trip on phase loss
B007
Restart frequency threshold
B012/
Level of electronic thermal setting
B212/
B312
B013/
Electronic thermal characteristic
B213/
• 00 Reduced torque • 01 Const. torque
B313
• 02 V/f free-setting
B015
Free setting, electronic thermal freq. (1)
B016
Free setting, electronic thermal current (1)
B017
Free setting, electronic thermal freq. (2)
B018
Free setting, electronic thermal current (2)
B019
Free setting, electronic thermal freq. (3)
B020
Free setting, electronic thermal current (3)
B021
Overload restriction operation mode
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
• 03 Enabled for accel, decel, constant
speed
Name / Description
• 01 Enable
Default Value
of each inverter
19
–FE / –FU /
–FR
00
1.0
1.0
00
00
0.00
1.0
Rated current
01 / 01 / 00
0.
0.0
0.
0.0
0.
0.0
01
Set
Value