Riello RL 190 Instrucciones De Instalación, Uso Y Mantenimiento página 27

Quemadores de gasóleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SIGNAL
FAULT
Rusty pump internal
parts
Noisy pump, unstable
pressure
Pump unprimes after
prolonged pause
Pump leaks light oil
Smoke in flame
- dark Bacharach
- yellow Bacharach
Dirty combustion head
10 led blinks
The burner goes to lock-
out
Faults - Possible causes - Solutions
PROBABLE CAUSE
52 - Water in tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Suck water from tank bottom with separate pump
53 - Air has entered the suction line. . . . . . . . . . . . . . . . . . . . Tighten connectors
- Depression value too high (higher than 35 cm Hg):
54 - Tank/burner height difference too great . . . . . . . . . . . . . Feed burner with loop circuit
55 - Piping diameter too small . . . . . . . . . . . . . . . . . . . . . . . . Increase
56 - Suction filters clogged. . . . . . . . . . . . . . . . . . . . . . . . . . . Clean
57 - Suction valves closed . . . . . . . . . . . . . . . . . . . . . . . . . . . Open
58 - Paraffin solidified due to low temperature. . . . . . . . . . . . Add additive to light oil
59 - Return pipe not immersed in fuel . . . . . . . . . . . . . . . . . . Bring to same height as suction pipe
60 - Air enters suction piping . . . . . . . . . . . . . . . . . . . . . . . . . Tighten connectors
61 - Leakage from sealing organ . . . . . . . . . . . . . . . . . . . . . . Replace pump
62 - Not enough air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust head and fan gate, see page 12 and page 18.
63 - Nozzle worn or dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
64 - Nozzle filter clogged . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clean or replace
65 - Erroneous pump pressure . . . . . . . . . . . . . . . . . . . . . . . Adjust to between 10 - 14 bar
66 - Flame stability spiral dirty, loose, or deformed . . . . . . . . Clean, tighten in place, or replace
67 - Boiler room air vents insufficient . . . . . . . . . . . . . . . . . . . Increase
68 - Too much air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust head and fan gate, see page 12 and page 18.
69 - Nozzle or filter dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
70 - Unsuitable nozzle delivery or angle . . . . . . . . . . . . . . . . See recommended nozzles, page 11
71 - Loose nozzle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tighten
72 - Impurities on flame stability spiral . . . . . . . . . . . . . . . . . . Clean
73 - Erroneous head adjustment or not enough air . . . . . . . . Adjust, see page 18, open gate valve
74 - Blast tube length unsuited to boiler. . . . . . . . . . . . . . . . . Contact boiler manufacturer
75 - Connection or internal fault . . . . . . . . . . . . . . . . . . . . . . .
76 - Presence of electromagnetic disturbance. . . . . . . . . . . . Use the radio disturbance protection kit
25
GB
SUGGESTED REMEDY
Tab. G
6080

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

673 t1347561420011018

Tabla de contenido