8.2
Operating faults
FAULTS
The burner locks out during opera-
tion.
Faults / Solutions
POSSIBLE CAUSES
Valve lets too little gas through
The valve is faulty.
Earth probe.
Disappearance of the flame.
21
GB
SOLUTION
Check mains pressure and/or adjust the valve
as indicated in this manual.
Replace.
Check right position and, if necessary, adjust
as indicated herein.
Clean or replace the ionisation probe.
Check gas mains pressure and/or adjust the
valve as indicated in this manual.
20030020