17
• Install conduit and fittings as shown. To
minimize loosening due to pipe vibration, use
flexible conduit.
• Pull in power and ground wires, strip off 1/2 in
(13 mm) of insulation and terminate.
Power and ground wires
18
• Install lid. Torque = 1.02 to 1.47 Nm
• Apply insulation and cladding.
• Weather-seal the stand entry.
• Leave these instructions with the
end user for future reference.
WARNING: Explosion Hazard- Substitution of Components
May Impair Suitablity for Class I Division 2 (Zone 2)
AVERTISSEMENT- Risque d'explosion. La substitution de
composants peut rendre ce matériel inacceptable pour les
emplacements de classe i, division 2 (zone 2).
1/2 in
(13 mm)
3/4 in locknut
Water tight
conduit seal
conductors are
Conduit
nVent recommends the use
drain
of a conduit drain to prevent
water condensation build-up.
Weather seal
WARNING: Explosion Harzard- Do not disconnect
equipment unless power has been switched off or the area
is known to be Non-Hazardous.
AVERTISSEMENT- Risque d'explosion. Ne pas débrancher
l'appareil à moins d'avoir coupé l'alimentation électrique ou
à moins qu'il ne s'agisse d'un emplacement non dangereux
Make sure
not exposed.
nVent.com/RAYCHEM | 9