Regulatory Compliance and Safety Information Regulatory Compliance & Safety Information for Cisco Catalyst 9400 Series Switches
Statement 1002 DC Power Supply
Warning
When stranded wiring is required, use approved wiring terminations, such as closed-loop or
spade-type with upturned lugs. These terminations should be the appropriate size for the wires
and should clamp both the insulation and conductor.
Statement 1003 DC Power Disconnection
Warning
Before performing any of the following procedures, ensure that power is removed from the DC
circuit.
Statement 1004 Installation Instructions
Warning
Read the installation instructions before using, installing or connecting the system to the power
source.
Statement 1005 Circuit Breaker
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure
that the protective device is rated not greater than:
20A circuit breakers for AC-input power supply. 50A DC-rated circuit breakers for each input for
safety purposes - irrespective of whether the inputs are power from a single or separate DC
sources.
Statement applies to: AC and DC power supply modules, respectively
Regulatory Compliance and Safety Information Regulatory Compliance & Safety Information for Cisco Catalyst 9400
Series Switches
5