Logging
Refer to "Logging Function" earlier in this manual. In the Logging (Record)
mode, the following values are recorded for every phase (L1, L2, L3):
•
Active power (P)
•
Apparent power (S)
•
Reactive power (Q)
•
Power factor (PF)
•
Cos phi (cosϕ)
•
Distortion power (D)
•
Accumulated values (kWh, kVAh, kVARh)
These values can be recorded in the instrument, downloaded and evaluated
with Power Log software.
Events
Select Events with the rotary switch.
This measuring mode records the voltage of every phase (L
of voltage dips, swells or interruptions (recorder function).
This function exclusively works with the recorder function.
Before you start the measurement, select the desired threshold value with
Menu/Esc (under recording adjustments). After the measurement has started
the following message appears on the display.
. . .
waiting for events
The Logger is now in the Trigger mode. If an event on one of the phases
occurs, the recording is started automatically and lasts for 4 minutes. The MIN
and MAX values of the half-cycle RMS values are shown as waves. The
screenshots recorded by this method are saved as individual pictures and can
be viewed later, or the data can be displayed with the Power Log software. A
total of 999 events can be recorded. In the LC display the phase and the
number of recordings are displayed.
Power Logger
Measuring Functions
, L
, L
) in cases
1
2
3
23