Approvals
Hazardous Locations
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups E, F, G
Class III
– WS
CLI, ZN1, AEx e II T*
Ex e ll T*
(2)
BR-Ex e II
(JBM-100-A only*)
JBS-100-A is IECEx certified for use with:
BTV-CR/BTV-CT:
QTVR-CT:
XTV-CT:
KTV-CT:
VPL-CT:
(1)
Except VPL
*For system Temperature Code, see heating cable or design documentation
(2)
Except KTV-CT
Kit Contents
Itemt Qty
Description
A
1
Stand assembly
B
1
Core sealer
C
1
Green/yellow tube
D
1
Cable lubricant
E
1
Cable tie
F
1
Lid
G
1
Box with terminal blocks
WARNING:
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings
and carefully follow all of the installation instructions.
• To minimize the danger of fire from sustained
electrical arcing if the heating cable is dam-
aged or improperly installed, and to comply with
the requirements of Tyco Thermal Controls,
agency certifications, and national electrical codes,
ground-fault equipment protection must be used.
Arcing may not be stopped by conventional circuit
breakers.
(1)
IECEx BAS 06.0043X
IECEx BAS 06.0045X
IECEx BAS 06.0044X
IECEx BAS 06.0046X
IECEx BAS 06.0048X
.
• Component approvals and performance are based
on the use of Tyco Thermal Controls -specified
parts only. Do not use substitute parts or vinyl
electrical tape.
• The black heating cable core and fibers are
conductive and can short. They must be properly
insulated and kept dry.
• Damaged bus wires can overheat or short. Do not break
bus wire strands when scoring the jacket or core.
• Keep components and heating cable ends dry
before and during installation.
• Use only fire-resistant insulation materials, such as
fiberglass wrap and flame-retardant foam.
JBS-100-A, A6
Single Entry Power Connection with
Junction Box
Installation Instructions
Description
The JBS-100-A and JBS-100-A6 are NEMA 4X-rated power connection
kit. It is designed for use with Raychem BTV-CR, BTV-CT, QTVR-CT,
XTV-CT, KTV-CT and VPL-CT industrial parallel heating cables.
The JBS-100-A6 utilizes larger terminal blocks to accommodate up to
6 AWG power wires.
This kit may be installed at temperatures as low as –40°F (–40°C). For
easier installation store above freezing until just before installation.
For technical support call Tyco Thermal Controls at (800) 545-6258.
Tools Required
• Wire cutters
• Adjustable pliers
• Utility knife
• 1/4 in or smaller flat-blade screwdriver
• Needle nose pliers
• Large slotted screwdriver
• Marker
• Wire stripper (for VPL-CT)
Additional Materials Required
• Pipe strap
• GT-66 or GS-54 glass cloth tape
Optional Materials
• Recommended conduit drain: JB-DRAIN-PLUG-3/4IN P/N 278621-000
• Small pipe adapter for 1 in (25 mm) and smaller pipes:
Catalog number JBS-SPA P/N E90515-000
A
B
C
D
CAUTION:
Health Hazard: Prolonged or repeated contact with
the sealant in the core sealer may cause skin irrita-
tion. Wash hands thoroughly. Overheating or burn-
ing the sealant will produce fumes that may cause
polymer fume fever. Avoid contamination of cigarettes
or tobacco. Consult MSDS VEN0033 for further
information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300.
Non-emergency health and safety information:
(800) 545-6258.
G
F
E

Publicidad

loading

Resumen de contenidos para Raychem JBS-100-A

  • Página 1 Installation Instructions Description The JBS-100-A and JBS-100-A6 are NEMA 4X-rated power connection kit. It is designed for use with Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT and VPL-CT industrial parallel heating cables. The JBS-100-A6 utilizes larger terminal blocks to accommodate up to 6 AWG power wires.
  • Página 2 JBS-100-A, A6 Installation Instructions Heating cable types Outer jacket Outer jacket Braid Outer Braid jacket Inner jacket Braid Heating element Inner jacket Inner jacket Bus wire connection Conductive fiber Conductive core Clear jacket Spacer Insulated bus wire Bus wire Bus wire...
  • Página 3 JBS-100-A, A6 Installation Instructions BTV and QTVR XTV and KTV • Push braid back to create a pucker. • Push braid back to create a pucker. • At pucker use a screwdriver to • At pucker use a screwdriver to open braid.
  • Página 4 JBS-100-A, A6 Installation Instructions • Push braid back and bunch as tight as possible. 6" (152 mm) • Lightly score inner jacket around and down as shown. • Peel off inner jacket. • Unwind heating element, cut and remove as shown.
  • Página 5 JBS-100-A, A6 Installation Instructions • Mark the jacket as shown. CAUTION: Health Hazard. Wash hands after contact with sealant. Consult material safety data sheet VEN0033. • If needed, re-twist and straighten bus wires, then insert into the guide tubes as shown.
  • Página 6 JBS-100-A, A6 Installation Instructions • Fasten stand to pipe with label facing Note: For 1" (25 mm) desired direction of box opening. Do not and smaller pipes use pinch heating cable. adapter (purchased • Loop and tape extra heating cable to pipe.
  • Página 7 JBS-100-A, A6 Installation Instructions This kit uses spring clamp style terminals. Terminals use a steel spring to clamp the wire to provide improved vibration resistance, reduced maintenance and faster installation. To connect wires, firmly insert a slotted screwdriver into the square hole ( ) to open the spring.
  • Página 8 JBS-100-A, A6 Installation Instructions 3/4" locknut • Install conduit and fittings as shown. To minimize loosening due to pipe Make sure vibration, use flexible conduit. Water tight conductors are conduit seal • Pull in power and ground wires, strip not exposed.
  • Página 9: Instruções De Instalação

    Instruções de instalação Descrição A JBS-100-A e a JBS-100-A6 são kits de conexão de alimentação com classifi- cação NEMA 4X. É projetada para uso com os cabos paralelos de aquecimento industrial modelos BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT e VPL-CT da Raychem.
  • Página 10 Instruções de instalação da JBS-100-A, A6 Tipos de cabo aquecedor Capa externa Capa externa Blindagem Capa externa Blindagem Capa interna Blindagem Elemento de aquecimento Capa interna Capa interna Conexão do fio condutor Fibra condutiva Núcleo condutivo Capa transparente Espaçador Fio condutor isolado...
  • Página 11 Instruções de instalação da JBS-100-A, A6 BTV e QTVR XTV e KTV • Recue a blindagem para criar uma • Recue a blindagem para criar uma dobra. dobra. • Na dobra, use uma chave • Na dobra, use uma chave de...
  • Página 12 Instruções de instalação da JBS-100-A, A6 • Pressione a blindagem para trás e agrupe o mais apertado possível. 6 pol. • Corte ligeiramente ao (152 mm) redor da capa interna e longitudinalmente como mostrado. • Retire a capa interna. • Desenrole o elemento de aquecimento, corte e retire como mostrado.
  • Página 13 Instruções de instalação da JBS-100-A, A6 • Marque a capa CUIDADO: Risco para a saúde. como mostrado. Lave as mãos depois de entrar em contato com o vedante. Consulte a Ficha de Informações de Segurança de Produto Químico (FISPQ) VEN0033.
  • Página 14 Instruções de instalação da JBS-100-A, A6 • Fixe o suporte no tubo com a etiqueta voltada Nota: Para tubos de 25 mm para a direção desejada de abertura da caixa. Não (1 pol.) ou menores, use o aperte o cabo aquecedor.
  • Página 15 Instruções de instalação da JBS-100-A, A6 Este kit usa terminais estilo grampo com mola. Os terminais usam uma mola de aço para apertar o fio e proporcionar resistência melhorada à vibração, manutenção reduzida e instalação mais rápida. Para ligar os fios, introduza firmemente uma chave de fendas no furo quadrado ) para abrir a mola.
  • Página 16 Instruções de instalação da JBS-100-A, A6 Contraporca de 3/4 pol. • Instale o conduíte e as conexões como mostrado. Para minimizar o afrouxamento Os condutores devido a vibração do tubo, use conduíte Vedação hermética não devem flexível. do conduíte ficar expostos.
  • Página 17 Instrucciones de instalación Descripción JBS-100-A y JBS-100-A6 son kits de conexión con calificación NEMA 4X. Se han diseñado para su uso con los cables calefactores paralelos de aplicación industrial Raychem BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT y VPL-CT.
  • Página 18 Instrucciones de instalación de JBS-100-A, A6 Tipos de cables calefactores Funda exterior Funda exterior Malla Funda Malla exterior Funda interior Malla Resistencia Funda interior Funda interior Conexión de cable de bus Fibra conductora Núcleo conductor Funda transparente Separador Cable de bus aislado...
  • Página 19 Instrucciones de instalación de JBS-100-A, A6 BTV y QTVR XTV y KTV • Empuje la malla hacia atrás para for- • Empuje la malla hacia atrás para for- mar un pliegue. mar un pliegue. • Utilice un destornillador para • Utilice un destornillador para...
  • Página 20 Instrucciones de instalación de JBS-100-A, A6 • Empuje la malla hacia atrás tanto como sea posible. 152 mm • Corte ligeramente la (6 pulg.) funda interior alrededor y a lo largo como se indica. • Pele la funda interior. • Desenrolle la resistencia, cór- tela y retírela como se indica.
  • Página 21 Instrucciones de instalación de JBS-100-A, A6 • Marque la funda como se indica. PRECAUCIÓN: Riesgo para la salud. Lávese las manos después del contacto con el sellador. Consulte la ficha de datos de seguridad VEN0033. • Si es necesario, tuerza y enderece los cables de bus e introdúzcalos en los tubos guía tal como se indica.
  • Página 22 Instrucciones de instalación de JBS-100-A, A6 • Fije el soporte al conducto con una etiqueta Nota: Para los conductos de orientada en la dirección que se desee para la 25 mm (1 pulg.) y más apertura de la caja. No aprisione el cable cale- pequeños utilice un...
  • Página 23 Instrucciones de instalación de JBS-100-A, A6 Con este kit se utilizan terminales con sujeción de muelle. Los terminales cuentan con un muelle de acero para sujetar el cable y conseguir mayor resistencia a las vibraciones, menos necesidad de mante- nimiento y una instalación más rápida.
  • Página 24 Instrucciones de instalación de JBS-100-A, A6 • Instale el conducto y los empalmes de Contratuerca de la manera indicada. Utilice un conducto 19 mm (3/4 pulg.) flexible para reducir el aflojamiento pro- Compruebe que los Junta de conducto vocado por la vibración de las tuberías.

Este manual también es adecuado para:

Jbs-100-a6