Descargar Imprimir esta página

ABB RC/A 8.1 Instrucciones De Montaje página 15

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 36
Technical Data (excerpt)
Power supply / input voltage:
Voltage range
Additional input voltage
Optional auxiliary power supply
Power loss
®
ABB i-bus
EIB:
Bus current consumption
Slots:
Number
Control and display elements:
Red LED and button
4 yellow LEDs and buttons
1 rotary selector switch
Connections:
Main power supply / input voltage
EIB
Additional input voltage
Optional auxiliary power supply
Conductor cross-sections
Design:
Type of installation
Housing, colour
Dimensions (WxHxD)
Enclosure
EN
90...264 V AC, 50/60 Hz for 3-phase connection
90...264 V AC, 50/60 Hz for 2-phase connection
190...264 V AC, 50/60 Hz for 1-phase connection
24 V DC, for wiring the direct input voltage
to 24 V DC modules
10...14 V DC, for backup or operation independent
of the mains electricity network
max. 4 W (without modules)
<1 mA
8 (Ml ... M8) accept any module type
For assigning the physical address
For status indication and manual operation
of the module function
For the selection of the module slot to be operated
5-pole plug-in screw type terminal
2-pole plug-in screw type terminal
3x2-pole plug-in screw type terminal
2-pole plug-in screw type terminal
Power supply / input voltage: 0.5...4.0 mm
Others: 0.2...2.5 mm
0.2...4.0 mm
Surface mounting device, screw fastening
plastic housing, grey, halogen-free
270 x 316 x 50 mm
IP 54 to DIN 60529
2
flexible wire
2
solid conductor
2

Publicidad

loading