Commissioning
3.4 Setting the Parameters
Select Pipe Configuration
1. Scroll down to [Pipe Config] and press the <Right Arrow>.
2. Select a configuration that approximates the conditions upstream of your transducer
3. Press the <Right Arrow> to save the selection.
Select Anomaly Diams
1. Trigger <Right Arrow> sensor to select [Anomaly Diams]..
2. Trigger <Right Arrow> to select "=" sign.
3. Trigger <Up/Down Arrows> to select number of pipe diameters.
4. Trigger <ENTER> to save selection.
5. To return to the top menu level, continue to trigger the <Left Arrow>.
Table 3- 4
Pipe Configuration Option List Definitions
Fully Developed
1 Elbow
Dble Elbow+
Dble Elbow-
Valve
Expander
Reducer
Norm Entry
Header Inlet
Intrusions
26
mounting location. (Refer to the Pipe Configuration Option List Definitions table.)
Options
Fully developed flow, as would be expected for very long
straight pipe runs or installation downstream of a flow
condition.
Single 90 degree Elbow upstream of transducer installation.
Double out-of-plane Elbows upstream of transducer
installation.
Double in-plane Elbows upstream of transducer installation.
Not available at this time.
Pipe expansion upstream of transducer installation.
Pipe reduction upstream of transducer installation.
Not available at this time.
Header or pipe manifold upstream of transducer installation.
Not available at this time.
Operating Instructions (Compact), 1/2009, CQO:QSG005 Revision B
Definitions