3.4

Setting the Parameters

Flowmeter Programming
Note
Before creating a site select English or metric units from the Meter Facilities menu.
Select Meter Type
1. After power-up, use the Magnetic Wand to trigger the <ENTER> sensor and access the
2. Trigger the Right Arrow> sensor.
3. Trigger <Up/Down Arrows> to select [2 Channel Flow]
4. Trigger <ENTER> sensor to select meter type: [Channel 1 Clamp-on] appears.
5. To select [Channel 1 Clamp-on] mode, trigger <Right Arrow> sensor.
6. Trigger <ENTER> sensor to select mode. [Channel Setup] menu will appear.
Create a Site
1. Trigger <Right Arrow> and then <Up/Down Arrows> to select [Create/Name Site].
2. Trigger <Right Arrow> again to select the "?" symbol (see figure below right).
3. To create site name use the <Up/Down> and <Right Arrow> to select a name.
SITRANS FUG1010 Quick Start
Operating Instructions (Compact), 1/2009, CQO:QSG005 Revision B
top level of the Installation Menu.
Note
Select [2 Channel Flow] if measuring two different pipes and [Dual Path Flow] if sensors
are mounted on the same pipe.
Commissioning
3.4 Setting the Parameters
23