6.1 Menu OPERATION

Start communication by pointing the R100 at the
CIU unit.
When communication between the R100 and the
CIU unit has been established, the OPERATION
menu appears in the display.
6.1.1 CIU unit and pump status
This display depends on the operating mode
selected in display "P1, operating mode".
See section 6.1.3 Operating mode.
The CIU unit indicates its own status:
OK
Alarm
Warn
"!" (indicates no contact with an already detected
pump).
A flashing P# indicates pump activity.

6.1.2 Fault indications

Fault indications are divided into two sections:
System alarms and warnings
Pump alarms and warnings.
System alarms and warnings
These displays show examples of a system alarm
and a system warning.
If a system fault has occurred, the cause will appear
in this display. The value (3) is the fault code.
See section 7.1.1 System alarms and warnings.
The fault indication can be reset in this display. If the
fault cause has not disappeared when resetting is
attempted, this will be indicated in the display.
Pump alarms and warnings
These displays show examples of a pump alarm and
a pump warning.
If a pump fault has occurred, the cause will appear in
this display. The value (9) is the fault code.
See section 7.1.2 Pump alarms and warnings.
The fault indication can be reset in this display. If the
fault cause has not disappeared when resetting is
attempted, this will be indicated in the display.
6.1.3 Operating mode
This display is used to set the operating mode and
control source for each individual pump.
The pump will run in this mode until it is switched off.
When the power supply is switched on again, the
pump will start in "Auto" mode.
Select an operating mode:
Auto (controlled by built-in sensors).
Start (the pump is running until an alarm is
generated or the pump is set to "Stop" or "Auto").
Stop (stopped).
Pump down (drains the pump pit).
Level control (controlled by the built-in level
pressure sensor).
R100 (R100 remote control).
Remotely (SCADA).