Features
Note: All GRAFIK Eye wallstations must be assigned a
unique address.
1.Put the GRX-IO in "Talk" mode. Press and hold the
program button for 3 to 5 seconds until:
• the first CCO Output LED blinks, OR
• the first four CCO Output LEDs begin to cycle.
2.Identify the GRAFIK Eye Control Unit(s) that will
"Listen" to this GRX-IO. Press and hold the Control
Unit's Scene 1 button for 3 seconds until the LEDs flash
in unison, showing that the Control Unit is "listening."
Repeat for each Control Unit that should listen to this
GRX-IO.
3a. 4S or 4Q Functions: Take the GRX-IO out of "Talk"
mode. Press and hold the program button for 3 to 5
seconds until the CCO Output LEDs stop cycling or
blinking.
3b. 4PS or OS functions: Each input must be
programmed separately.
Press the program button to cycle through each
input. These represent a partition switch, occupant
sensor, etc. The corresponding CCO Output LED
will blink.
Program GRAFIK Eye Control Unit(s) to
communicate with the GRX-IO by using the above
procedure.
When the fifth input is programmed, pressing the
program button on the GRX-IO will take the GRX-
IO out of "Talk" mode.
R
Note: To make a GRAFIK Eye Control Unit stop "listening"
to a GRX-IO, put the GRX-IO in "Talk" mode, then
press and hold the OFF button on the GRAFIK Eye
Control Unit until the LEDs stop blinking. Take the
GRX-IO out of "Talk" mode.
GRAFIK Eye