GRX-IO Operating Modes and DIP Switch Settings
• Operating mode can be selected by setting DIP
switches 5 through 8. Inputs and outputs may be
maintained or momentary as indicated.
• May be programmed to control any combination of
one to eight GRAFIK Eye 3000 or 4000 Series control
units.
Mode
DIP Switches
5
6 7 8
Scene
Selection
Special
Functions
2
Partitioning
Occupant
Sensor
Switch up (On)
Switch down (Off)
1
Scenes trigger the position of motorized window shades or projection screens.
2
Movable walls toggle control units between "in combination" and "independent" modes of operation. Each input is set up to operate the
control units associated with a movable wall (or walls).
• When a motorized wall opens, the wall's switch contact closes. The control units now work "in combination." Scene changes at one
control unit occur on all the associated control units.
• When a wall closes, the switch contact opens. The control units return to independent operation.
3
If an occupant sensor input provides momentary closure, use scene selection mode.
Contact closures invoke:
Input 1
Input 2
Scene 1
Scene 2
Scene 5
Scene 6
Scene 9
Scene 10
Scene 13
Scene 14
Scene 1
Scene 2
Scene 5
Scene 6
Scene 9
Scene 10
Scene 13
Scene 14
Sequence
Zone lockout
scenes 1-4
allows
temporary
Sequence
adjustments.
scenes 5-16
No changes to
preset scenes.
Sequence
scenes 1-4
Sequence
scenes 5-16
Wall 1
Wall 2
Wall 1
Wall 2
Sensor input toggles Control Units between scene 1 and off.
Sensor input turns Control Units off. Occupant must turn lights on. Maintained only
R
• For scene selection and special function modes,
one control unit or a group of control units may be
assigned to be operated by the GRX-IO.
• With partitioning and occupant sensor modes, a
different control unit or group of control units may be
assigned for each I/O closure.
Input 3
Input 4
Input 5
Scene 3
Scene 4
Off
Scene 7
Scene 8
Off
Scene 11
Scene 12
Off
Scene 15
Scene 16
Off
Scene 3
Scene 4
Off
Scene 7
Scene 8
Off
Scene 11
Scene 12
Off
Scene 15
Scene 16
Off
Scene
"Panic" mode
Not
lockout
turns lights
used
disables
full on (to
scene
scene 16),
buttons.
locks Control
Units.
Wall 3
Wall 4
Wall 5
Wall 3
Wall 4
Wall 5
GRAFIK Eye
and GRAFIK Systems Installation Instructions
®
Inputs:
Outputs:
Maintained or
Maintained
momentary
Maintained or
Momentary
momentary
Maintained only
Maintained
Momentary only Maintained
Momentary only
Maintained
Maintained only
Maintained
3
Maintained only
Maintained
3
Maintained
1
5

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Grafik eye omx-ioGrafik eey grx-ioGrafik eey omx-io

Tabla de contenido