Unscheduled Maintenance; Possible Faults And Solutions - Sime Brava Slim HE 25 T Manual De Instalación Y Mantenimiento

Ocultar thumbs Ver también para Brava Slim HE 25 T:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.5

Unscheduled maintenance

If replacing the electronic board , the user MUST set the
parameters as indicated in the table.
Type
No.
Description
Index showing boiler power in kW
PAR
01
0 = 25T
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
heating only
PAR
02
2 = hot water tank with sensor
3 = two programmer
4=instant with solar power input
5 = open vent
Gas Type Configuration
PAR
03
0 = G20; 1 = G31
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the entire phase of "Self-calibrating procedure" described
in the specific section.
If the gas cock and/or the ignition/detection electrode , and/or the
burner
, and/or the fan are replaced, the user must still carry out
the entire phase of "Self-calibrating procedure" described in
the specific section.
4.6

Possible faults and solutions

LIST OF MALFUNCTION/FAULT ALARMS
Type
No.
Fault
Low water pressure in
ALL
02
system
High water pressure in
ALL
03
system
Domestic hot water
ALL
04
sensor fault
ALL
05
Delivery sensor fault
ALL
06
No flame detection
Sensor or safety
ALL
07
thermostat intervenes
Fault in the flame
ALL
08
detection circuit
84
All manuals and user guides at all-guides.com
Type
Setting
0
2
0 or 1
Solution
- Restore pressure
- Check for any leaks in
the system
- Empty the system via
the drain valve on the
hydraulic assembly and
bring the pressure to
approximately 1.2 bar
- Check connections
- Replace the sensor
- Check connections
- Replace the sensor
- Check the integrity of
the electrode and check
that it is not grounded
- Check gas availability
and pressure
- Check the integrity of
the gas valve and the
card
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or
the thermostat
- Check that the pump
impeller is not blocked
- Check the integrity of
the electrode and check
that it is not grounded
- Check gas availability
and pressure
- Check the integrity of
the gas valve and the
card
No.
Fault
No water circulating in
ALL
09
the system
ALL
10
Auxiliary sensor fault
Gas valve modulator
ALL
11
disconnected
Incorrect configuration
ALL
12
of the open /sealed
chamber
Smoke probe
ALL
13
intervention
ALL
14
Smoke probe fault
Fan check cable
ALL
15
disconnected
ALL
18
Condensate level fault
Maximum number of
ALL
28
consecutive resets
reached
Fault due to low network
ALL
37
voltage.
Incorrect network
ALL
40
frequency detected
Flame loss more than 6
ALL
41
consecutive times
ALL
42
Button fault
Open Therm
ALL
43
communication fault
Self-calibrating
ALL
62
procedure is required
Incorrect positioning of
ALL
72
the delivery sensor
Block due to combustion
ALL
81
during start-up
Irregular combustion
ALL
83
(temporary error)
Block due to clogging in
ALL
96
smoke outlet
Frequent relief valve
-
-
intervention
Limited production of
-
-
domestic hot water
EN
Solution
- Check the rotation
of the system pump
impeller
- Check the electrical
connections
- Replace the pump
- Check PAR
02 "hydraulic
configuration"
- Check the electrical
connection
- Check the electrical
connection
- Set the parameter
PAR 04 (Combustion
configuration) to 0
- Replace the smoke
probe
- Contact the Technical
Assistance Centre
- Replace the smoke
probe
- Check the electrical
connection of the
smoke probe, if the
problem is not resolved,
contact the Assistance
Centre
- Check the connection
cable between the fan
and the board
- Check for any clogging
in the pipe which takes
the condensate to the
siphon
- Check that the siphon
is not clogged
- Contact the Technical
Assistance Centre
- Check with tester
- Contact network
provider (ENEL)
- Contact network
provider (ENEL)
- Check the detection
electrode
- Check the gas supply
(open valve)
- Check mains gas
pressure
- Check that buttons are
working
- Check the electrical
connection of the
remote control
- Carry out the self-
calibrating procedure
(see the specific
section)
- Check that the delivery
sensor is attached to
the delivery pipe
- Check for blockage in
chimney
- Bleed the air from the
gas circuit
- Check for blockage in
chimney
- Check for blockage in
chimney
- Check circuit pressure
- Check expansion vessel
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot
water circuit valve