INSTALLER CONNECTIONS
KM3 Caldaia
Permette di attivare una caldaia come elemento di inte-
grazione o in sostituzione per il riscaldamento dell'impianto.
Soluzione 1
Impianto con pompa di calore e caldaia con accumulo
inerziale.
Soluzione 2
Impianto con pompa di calore e caldaia senza accumulo
inerziale.
Boiler control
A) REPLACEMENT: the boiler is only enabled if the outside
air temperature is less than the value of parameter 0307
and the compressor is off, figure 3.
To enable boiler activation in REPLACEMENT mode set
parameter 0306=1 and 010h = 1
If the heat pump shuts down due to an alarm the boiler is
activated automatically regardless of the outside air temper-
ature.
In REPLACEMENT mode the activation delay time is
ignored, and the boiler is activated immediately if necessary.
B) SUPPLEMENTARY: the boiler operates in supplemen-
tary heating mode, together with the compressor, to satisfy
the heating load.
Supplementary heating for low outside air temperature
The boiler is enabled only when the outside air temperature
is less than the value of parameter 0307, figure 3.
To enable the supplementary heating for outside air temper-
ature set parameter 0306 = 1 and 010h = 0
Boiler operation reflects the trend in water temperature, as
shown on the graph in figure 4.
24
PBM 20÷40 EN
1
7 8
43 44
2
7 8
43 44
Boiler operating parameters in REPLACEMENT mode
Description
Activation Boiler
0 = Boiler not enabled
1 = Boiler enabled
Type of boiler operation
0 = Supplementary
1 = Replacemen
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
boiler
Set the parameters following the sequence described in
the table
Boiler operating parameters in SUPPLEMENTARY mode
for outside temperature
Description
Activation Boiler
0 = Boiler not enabled
1 = Boiler enabled
Type of boiler operation
0 = Supplementary
1 = Replacemen
Activation with low outside air
temperature
0 = Function not enabled
1 = Function enabled
Outside air temperature to enable
boiler
Minimum outside air temperature
for heat pump operation (make
sure the value set is the same as
shown in the table)
Boiler activation delay time (allows
the heat pump to reach steady
operation and thus avoid activat-
ing the boiler when not needed)
Integration time to activate boiler
Set the parameters following the sequence described in
the table
U I A
BT9
Boiler
BT9
Boiler
Menu
Parameter
Value to be
UOM
no.
set
Mn03
0301
1
Mn01
010h
1
Mn03
0306
1
Mn03
0307
Example
-5°C
Menu
Parameter
Value to be
UOM
no.
set
Mn03
0301
1
Mn01
010h
0
Mn03
0306
1
Mn03
0307
Example
-5°C
Mn03
0311
-20
Mn06
0618
60
Mn06
0619
600
°C*sec
°C
°C
°C
min.