MAINTENANCE AND SERVICE
Alarm code
A097
Temperature probe N-ThC n.3
A098
Address setting error on zone remote terminal
A099
Temperature probe N-ThC n.4
A100
Address setting error on zone remote terminal
A101
Temperature probe N-ThC n.5
A102
Address setting error on zone remote terminal
A114
Solar/pool module address setting error
A115
Solar/pool module general alarm
A116
Master unit not connected, cascade control
A117
Slave unit not connected, cascade control
A120
Water temperature too high in mixed circuit, expansion module, expansion module 3
A121
Temperature probe N-ThC n.6
A124
humidity probe N-ThC n.1
A125
humidity probe N-ThC n.2
A126
humidity probe N-ThC n.3
A127
humidity probe N-ThC n.4
A128
humidity probe N-ThC n.5
A129
humidity probe N-ThC n.6
MAINTENANCE AND SERVICE
SYSTEM emergency operation
If the heat pump is not working correctly or the compressor
has shut down, emergency operation can be activated.
Emergency operation involves heating the water using the
electric heaters available on the system (outlet, storage
tank).
The compressor remains off.
To enable manual operation of system heaters, set parame-
ter 0620 = 1 (manual)
DOMESTIC HOT WATER emergency operation
If the heat pump is not working correctly or the compressor
has shut down, emergency operation can be activated.
Emergency operation involves heating the domestic hot
water using the electric heater inside the storage tank.
To enable manual operation of DhW storage heaters, set
parameter 0202 = 1

SHUTTING DOWN FOR LONG PERIODS

After deactivating the heat pump:
- Disconnect the unit from the power supply.
- Make sure the remote keypad is in the "OFF" position.
- Place QF1 in the OFF position (see wiring diagram).
- Deactivate the indoor terminal units by placing the switch
of each unit in the "OFF" position.
- Close the water valves.
If the outside temperature may fall below zero; there is
the risk of freezing.
The water circuit MUST BE EMPTIED AND CLOSED (if
draining after operation in heat pump mode, beware that
72
PBM 20÷40 EN
Cause
Description
Type of outlet electric heater oper-
ation
0 = Supplementary
1 = Replacement
Enable manual heater operation
Set the parameters following the sequence described in
the table
Description
Electric heater operating mode:
0 = DhW production disabled
1 = heat pump only
2 = Electric heater only
3 = heat pump + electric heater
the water may be hot), or antifreeze must be added in
the proportion recommended by the manufacturer.
It is recommended to use non-toxic food grade
antifreeze, compliant with the standards in force in the
countries where the unit is used, if domestic hot water
production is also featured.
If the mains switch is turned to "off" for more than four
hours, after turning it on and before reactivating the unit,
leave the power on but the unit deactivated for at least
two hours to preheat the oil in the compressor sump.
Solution
Check connections
Probe faulty or disconnected
Check connections
Check address
Check connections
Probe faulty or disconnected
Check connections
Check address
Check connections
Probe faulty or disconnected
Check connections
Check address
Check connections
Check address
Check connections
Probe faulty or disconnected
Check connections
Probe faulty or disconnected
Check connections
Probe faulty or disconnected
Check connections
Probe faulty or disconnected
Check connections
Probe faulty or disconnected
Check connections
Probe faulty or disconnected
Check connections
Probe faulty or disconnected
Menu
Parameter
Default
no.
Mn01
010G
1
Mn06
0620
1
Menu
Parameter
Value to be
no.
set
Mn02
0202
1
A
A
UOM
UOM
A