SYSTEM CONFIGURATION
System number 2
Parameter configuration
Description
Description
System type (table 1)
Mixing valve ZONE 1
Type of mixing valve
0= 3-position
1= 0-10V
3-position valve travel time
HEATING compensation curve ZONE 1
Enable compensation curve 0= Disabled 1= Enabled
heating compensation curve number
Enable room temperature influence
0= Disabled
1= Enabled
Room Authority
MINIMUM outlet set point limit for curve
MAXIMUM outlet set point limit for curve
COOLING compensation curve ZONE 1
Enable compensation curve 0= Disabled 1= Enabled
Maximum outlet temperature set point limit in cooling mode (Tm1)
Minimum outside temperature corresponding to max. outlet
temperature (Te1)
Minimum outlet temperature set point limit in cooling mode (Tm2)
Maximum outside temperature corresponding to min. outlet
temperature (Te2)
HUMIDITY CONTROL ZONE 1
Enable compensation for room humidity, ZONE LT1
0= Disabled
1= Enabled
Room relative humidity value to start increasing water outlet temperature
set point
Maximum outlet temperature hysteresis corresponding to 100%
relative humidity
Enable contact hL1 as DEhUMIDIFIER (The contact closes and the
dehumidifier is activated when the humidity measured by the probe
on the A5 room controller exceeds the value set for parameter 0172)
HEATING compensation curve for HEAT PUMP MODE (THE TEMPERATURES MUST DIFFER FROM THOSE IN ZONE 1 & 2 BY AT
LEAST +3°C IN HEATING AND -3°C IN COOLING)
Enable compensation curve 0= Disabled 1= Enabled
Compensation curve number
Enable room temperature influence
0= Disabled
1= Enabled
Room Authority
MINIMUM outlet set point limit curve
MAXIMUM outlet set point limit curve
COOLING compensation curve for HEAT PUMP MODE (THE TEMPERATURES MUST DIFFER FROM THOSE IN ZONE 1 & 2 BY AT
LEAST +3°C IN HEATING AND -3°C IN COOLING)
Enable compensation curve 0= Disabled 1= Enabled
Maximum outlet temperature set point limit in cooling mode (Tm1)
Minimum outside temperature corresponding to max. outlet
temperature (Te1)
Minimum outlet temperature set point limit in cooling mode (Tm2)
Maximum outside temperature corresponding to min. outlet
temperature (Te2)
For systems with high temperature zone (example bathroom radiators) managed using a thermostat not supplied by Manufacturer, set the
hEATING compensation curve, parameter 0159, to a value so as to reach a suitable outlet temperature for radiators.
The mixed zone is managed according to the compensation curve set for parameter 0174.
* obligatory values for the present configuration
66
PBM 20÷40 EN
Parameter
Menu
Default
no.
Mn01
0101
Mn01
012T
Mn01
013B
150
Mn01
0167
Mn01
0174
0,7
Mn01
0178
Mn01
0179
30
Mn01
0180
23
Mn01
0181
45
Mn01
0169
Mn01
0132
20
Mn01
0133
23
Mn01
0134
18
Mn01
0135
36
Mn01
0171
Mn01
0172
70
Mn01
0173
15
Mn01
015A
Mn01
0152
Mn01
0159
Mn01
0163
Mn01
0164
30
Mn01
0165
30
Mn01
0166
48
Mn01
0154
Mn01
0128
20
Mn01
0129
23
Mn01
0130
18
Mn01
0131
36
U I A
Write set value
UOM
0
2*
0
sec
0
0
°C
°C
0
°C
°C
°C
°C
0
°C
0
1*
0
1
0
°C
°C
0
°C
°C
°C
°C
-
%
%
-
-
-
%
-