Baxi PBM-i 20 Manual Del Usuario página 124

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATION AND FUNCTIONS OF THE ROOM CONTROLLER
Domestic hot water production
1
Domestic hot water production not enabled
WARNING:
If domestic hot water production is featured on the heat pump, this function needs to be enabled.
Set parameter 0202, under menu "Mn02", choosing one of the following options:
1 = heat pump only (domestic hot water production with heat pump only)
2 = Electric heater only (domestic hot water production with electric heater only)
3 = heat pump + Electric heater (domestic hot water production with heat pump and electric heater, as described in the para-
graph "kM4 DhW storage electric heater (or Boiler)"
Parameter 0202 is factory set to 0=DhW disabled.
Selecting the domestic hot water set point
The domestic hot water temperature is measured by the probe installed inside the DhW storage tank.
1
4
• Press the knob to confirm
44
PBM 20÷40 EN
2
Press the
.
2
• Press thei
+
buttons together for 3
seconds
5
• Press the knob to confirm
3
• Domestic hot water production enabled
• The
symbol is displayed
3
x3 sec.
• Turn the knob and select the value of para-
meter 012
6
• Turn the knob and select parameter 0023
A
 

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pbm-i 30Pbm-i 40

Tabla de contenido