5. Commissioning, operation
5.2 Electrical mounting
Only connect cables and lines in an unpowered state!
Fine-stranded leads must be finished with end splices.
Cables used must comply with the respective requirements in terms of stability and
temperature, strain and mobility. Over-working the cable may cause fraying of the wire.
Connection cables must be run so that any mechanical damage is prevented. This
includes areas where wear may occur resulting in fraying of the wire.
When bending connection cables it cannot be bent within 25 mm [1 in] of the transition
region.
Connection cables are not to be in contact with hot surfaces (i. e. hot manifolds). Where
this cannot be achieved proper selection of electrical wire, transition or high-temperature
sleeve shall be used.
Colour coding of thermocouple cable
Thermocouple
Type J
Type K
Type E
Type T
Type N
WIKA operating instructions model TC52-M
Standard
IEC 60584
ASTM E230
DIN 43714
IEC 60584
ASTM E230
IEC 60584
ASTM E230
IEC 60584
ASTM E230
IEC 60584
ASTM E230
Positive
Black
White
Red
Green
Yellow
Violet
Violet
Brown
Blue
Pink
Orange
Negative
White
Red
Blue
White
Red
White
Red
White
Red
White
Red
19
EN