ENG
PREVENTION OF SIPHONING
Ensure that end of discharge hose is higher than water level in evaporator drain pan.
If condensate discharge point must be lower than drainpan then 1/4" discharge hose from pump must empty
into a larger diameter drain pipe at a higher level than drainpan.
THIS JOINT MUST INCORPORATE AN AIR BREAK TO PREVENT SIPHONING.
FOR FULL DETAILS ON SIPHONING, CONSULT ASPEN PUBLICATION: GUIDELINES FOR CORRECT INSTALLATION
OF DISCHARGE HOSING, ON LAST PAGES OF THIS MANUAL.
ES
PREVENCIÓ N DEL EFECTO SIFON
Cerciórese de que el extremo de la manguera de descarga esté en un nivel más alto que el nivel del agua en la
bandeja de desagüe del evaporador.
Si el punto de descarga de agua de condensación debe estar más abajo que la bandeja de desagüe, la
manguera de descarga de 1/4" de d.i. proveniente de la bomba debe vaciarse en una tubería de desagüe que
tenga un diámetro mayor y esté en un nivel más alto que la bandeja.
ÉSTE UNIÓN ENTRE EL TUBO y LA MANGUERA NO DEBE SER HERMÉTICA PERMITIENDO HAyA UN ESPACIO
ENTRE AMBAS SUPERFICIES DE CONTACTO PARA EVITAR EL EFECTO SIFON.
SI DESEA MAyORES DETALLES SOBRE EL SINFONAJE, CONSULTE LA PUBLICACIÓN DE ASPEN: PAUTAS PARA
LA CORRECTA INSTALACIÓN DE LA MANGUERA DE DESCARGA, EN ULTIMO PAGINAS DE ESTA MANUAL.
Checklist / Lista de verificación
ENG
ITEM
DESCRIPTION
Does pump voltage conform with evaporator
1
supply voltage?
Is actual power input sufficient to drive pump?
2
Is pump permanently energized regardless of
3
evaporator operation?
Is fuse installed?
4
Is overflow switch (gray and purple wires) correctly
5
wired into communication wire to ensure unit
will not operate in case of pump failure or blockage?
Is piping & wiring in accordance with
6
manufacturer's instructions?
Is pump correctly sized to handle condensate output
7
of evaporator?
Is maximum head within pump limits?
8
6
falSe ceIlINg /
TecHo falSo
eND of
DIScHarge Tube /
exTremo Del
maNguera De
DeScarga
ToP of breaTHer
Tube /
ParTe SuPerIor
Del Tubo
reSPIraDor
WaTer leVel IN DraIN TraY /
NIVel De agua eN la baNDeja De
DeSagÜe Del eVaPoraDor
ITEM
DESCRIPTION
Is discharge hose sized at 1/4" i.d. as per
9
manufacturer's instructions?
Is discharge hose watertight?
10
Is reservoir level?
11
Is float in position?
12
Is magnet facing upwards on float?
13
Is filter present in reservoir?
14
15
Has provision been made to prevent siphoning?
Is drain discharge hose clear of restrictions?
16
17
Is intake hose watertight?
Is breather tube installed and free of restrictions?
18
19
Is pump correctly connected to ensure water flow
towards discharge hose?
20
Is pump wrapped with damping material to
eliminate vibration
aIr break /
eSPacIo Del
aIre