Maximum Trip Time
RCD
AC G, A, B
AC G-S, A-S, B-S
AC G, A, B
AC G-S, A-S, B-S
RCD/FI-Tripping Current Measurement/Ramp Test ( I
Current Range
30 % to 110 % of
RCD rated current
Notes
[1] 30 % to 150 % for Type A I
30 % to 210 % for Type A I
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (≤10 mA)
50 % to 200 % for Type B
[2] 5% for Type B
Earth Resistance Test
Telaris ProInstall-200 only. This product is intended to be used to measure installations in
process plants, industrial installations, and residential applications.
Range
200 Ω
2000 Ω
Range: R
+ R
E
PROBE
2200 Ω
16000 Ω
52000 Ω
Note
[1] Without external voltages
Frequency
128 Hz
Live Circuit Detection
I
P
N
X 1
X 1
X 5
X 5
Step Size
[2]
10 % of I
[1]
N
P
>10 mA
N
P
= 10 mA
N
P
Resolution
0.1 Ω
1 Ω
[1]
Test Current
3.5 mA
500 μA
150 μA
Output Voltage
25 V
Inhibits test if terminal voltage >10 V ac is detected prior
to start of test.
Trip Time Limits
Less than 300 ms
Between 130 ms and 500 ms
Less than 40 ms
Between 50 ms and 150 ms
P
Measurement Range
Type G
Type S
300 ms/step
500 ms/step
Accuracy
±(3 % + 5 digits)
±(5 % + 10 digits)
29
)
N
Measurement
Accuracy
±5 %