Tripp-Lite SmartOnline Manual Del Propietário página 10

Ocultar thumbs Ver también para SmartOnline:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Operation
( continued )
3.3 Front Panel Indicator Lights
( continued )
"BYPASS" LED: This yellow LED will illuminate continuously when the
UPS system is in economy mode. The LED will flash when the UPS system is
bypass mode, indicating that the UPS system's DC/AC inverter is
deactivated. The red "FAULT" LED will also illuminate if the UPS system is
in bypass mode. During normal operation the bypass LED will illuminate
briefly when the unit is plugged in. If an internal fault or overload occurs, the
LED will flash repeatedly to show that connected equipment will receive
filtered AC line power, but will not receive battery power during a blackout.
In this case, contact Tripp Lite for service.
"FAULT" LED: This red LED will flash when the UPS system detects an
internal fault. If the condition persists after restarting the UPS system, see
Section 4: Troubleshooting.
"LOAD" LED: This green LED will illuminate when the UPS system is
receiving AC power. It also indicates that the % level LEDs (25%, 50%,
75%, 100%) are displaying the UPS load level.
"BATT" LED: This green LED will illuminate when the UPS system is
operating from battery power. It indicates that the % level LEDs (25%, 50%,
75%, 100%) are displaying the battery charge level. (The "ON BATT" LED
will also be illuminated.)
% Level LEDs: These dual-function LEDs will indicate the % level for
either the load level (if the "LOAD" LED is lit) or the battery charge level (if
the "BATT" LED is lit).
"OVERLOAD" LED: This red LED will illuminate continuously to indicate
that the UPS system's capacity has been exceeded. The UPS alarm will beep
continuously. Immediately unplug some equipment until the LED and alarm
go off. If the overload is not corrected immediately, the UPS system will go
from on-line to bypass mode.
"BATT LOW" LED: This yellow LED will illuminate when the UPS system's
battery charge level is low. The UPS alarm will beep until the batteries are
either depleted or adequately recharged.
"ON BATT" LED: This green LED will illuminate continuously to indicate
that AC line voltage is absent (or out of range) and the UPS system is
providing equipment with battery-derived AC power. The UPS system will
also beep every 2 seconds (unless silenced by the "ON/TEST" button) and
the % level LEDs (25%, 50%, 75%, 100%) will display the battery charge
level.
"REPLACE BATT" LED: This red LED will illuminate continuously and
the UPS alarm will beep every 2 seconds if the UPS system fails the
automatic self-test. Allow the UPS system to charge for at least 12 hours and
perform a self-test as described in Section 3.1: Front Panel Switches. If the
condition persists, contact Tripp Lite.