11.2 - POWER OF PHOTOCELLS AND AND
FUNCTIONAL TEST
Photocells can be powered to 24 Vac (FIG.1) or 12 Vdc (FIG.2).
Regardless of the selected function, the photocells can be tested
prior to each movement.
To enable the photocell test it is required to indicate the maximum
duration of the test in the parameter
test is not carried out.
POWER SUPPLY 24VAC
Connect the power supply of photocell receivers between
terminals E1 and E3 (COM).
Connect the power supply of photocell transmitters between
terminals E5 and E3 (COM).
NOTE: to facilitate wiring the terminals for the AC power supply
are double (E1 = E2 / E3 = E4)
WARNING: To carry out the test it is necessary that the
transmitter power of the photocells is connected to the terminals
E5 and E3 (COM)
A
40%
B
40%
C
40%
: if set to
, the
FO.TE
NO
FIG. 1
S1 S2 S3 S4 S5 S6 S7 S8 S9
RX
FIG. 2
S1 S2 S3 S4 S5 S6 S7 S8 S9
RX
+ -
POWER SUPPLY 12VDC
The DC power supply is available between terminals
H8 (+) and H7 (-).
ATTENTION: In order to perform the test, one of the relay options
must be used:
• REL1: connect the transmitter power supply between terminals
Z3 (+) and H7 (-) and connect the terminal H8 with the
terminal Z4, set the
REL1
• REL2: connect the transmitter power supply between terminals
Z5 (+) and H7 (-) and connect the terminal H8 with the
terminal Z6, set the
REL2
24Vac
FOT1
FOT2
a
parameter
DEFAULT =
FOT1
parameter
FOT2
(enabled when opening and closing)
12Vdc
FOT1
FOT2
- 35 -
parameter to
.
TEST
parameter to
.
TEST
E1 E2 E3 E4 E5
(no function)
NO
a
DEFAULT =
APCH
H7 H8
Z6
Z5
Z4
Z3
TX
Z2
Z1
TX
+ -