7.3

Setting

8021184.1ABM / 2020-12-21 | SICK
Subject to change without notice
Minimum distance between set sensing range and
background (white, 90%) in % of sensing range
y
25
20
6%/90%
1
15
18%/90%
10
2
5
0
0
50
100
150
(1.97)
(13.94)
(5.91)
1
Sensing range on black, 6 % remission
2
Sensing range on gray, 18 % remission
3
Sensing range on white, 90 % remission
Figure 3: Sensing range of up to 300 mm
Use
figure 5
and
see table 2, page 7
fails to behave in accordance with the table, check the application conditions,
„Troubleshooting table", page
Figure 4: Description of range areas
Sensing range setting
Sensor which it is not possible to set: The sensor is adjusted and ready for operation.
The sensing range is adjusted with the potentiometer (type: 270°). Clockwise rotation:
sensing range increased; counterclockwise rotation: sensing range reduced. We recom‐
mend placing the object within the sensing range, e.g.
range has been adjusted, the object is removed from the path of the beam, which
causes the background to be suppressed and the switching output to change
table
2].
Example:
Sensing range on black, 6%
x = 100 mm, y = (10% of 100 mm) =10 mm
90%/90%
3
x
200
250
300
(7.87)
(9.84)
(11.81)
Distance in mm (inch)
to check the function. If the switching output
10.
COMMISSIONING
white background (90%)
x
y
see
see table
3. Once the sensing
[see
7
9