Technical data
Ratings, fuses and typical power cables
1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors.
The horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses.
3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274 certifications.
4) IEC 61439-1: The drive is suitable for use on a circuit capable of delivering not more than 65 kA when protected by the fuses given in this
table.
5) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of the
other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other
conditions, size the cables according to local safety regulations, appropriate input voltage and the load current of the drive.
6) Typical drive losses when it operates at 90% of the nominal output frequency and 100% of the motor nominal current. See IEC 61800-9-2.
ACQ580-
Input
04-...
current
IEC ratings
I
I
1
2
A
A
U
= 400 V
n
505A-4
505
505
585A-4
585
585
650A-4
650
650
725A-4
725
725
820A-4
820
820
880A-4
880
880
ACQ580-
Input
04-...
current
IEC ratings
I
I
1
2
A
A
U
= 480 V
n
505A-4
483
505
585A-4
573
585
650A-4
623
650
725A-4
705
725
820A-4
807
820
880A-4
807
880
Terminal data
Screw size L1/U1, L2/V1, L3/W1, T1/U2, T2/V2, T3/W2 and UDC+, UCD- with +H356 and R+
Maximum accepted cable size
mm
M12
4 × (3 × 240)
Energy efficiency data (ecodesign)
Energy efficiency data according to IEC-61800-9-2 is available from the ecodesign tool.
(https://ecodesign.drivesmotors.abb.com).
Motor
Output
1)
current
power
I
I
P
P
LD
HD
LD
HD
DIN 43653
A
A
kW
kW
485
361
250
200
170M6012
575
429
315
250
170M6014
634
477
355
250
170M6014
715
566
400
315
170M6016
810
625
450
355
170M6269
865
725* 500
400
170M6269
Motor
Output
1)
current
power
I
I
P
P
LD
HD
LD
HD
DIN 43653
A
A
hp
hp
483
361
400
300
170M6012
573
414
450
350
170M6014
623
477
500
400
170M6014
705
566
600
450
170M6016
807
625
700
500
170M6269
807
625
700
500
170M6269
and R- with +D150: full-size terminals
AWG
2
4 × (3 × 500) MCM
Typical power
2)3)
Ultrarapid aR fuses
(Bussmann)
cable (Copper)
4)
DIN 43620
170M8557D
170M8557D
170M8557D
-
-
-
Typical power
2)3)
Ultrarapid aR fuses
(Bussmann)
cable (Copper)
4)
DIN 43620
170M8557D
170M8557D
170M8557D
-
-
-
Tightening torque
N·m
50...75
Technical data 59
Typical
5)
power loss
2
W
mm
3 × (3×95)
6492
3 × (3×120)
6840
3 × (3×150)
8046
3 × (3×185)
8108
3 × (3×240)
9652
3 × (3×240)
10887
Typical
5)
power loss
2
W
mm
3 × (3×95)
6492
3 × (3×120)
6840
3 × (3×150)
8046
3 × (3×185)
8108
3 × (3×240)
9652
3 × (3×240)
10887
Grounding terminal
Tightening torque
lbf·ft
N·m
37...55
20
Frame
size
6)
R10
R10
R10
R11
R11
R11
Frame
size
6)
R10
R10
R10
R11
R11
R11
lbf·ft
14.75

Publicidad