Statement 7004-Special Accessories; Statement 7005-Intrabuilding Lightning Surge And Ac Power Fault - Cisco NCS 500 Serie Manual Del Usuario

Tabla de contenido

Publicidad

Regulatory Compliance and Safety Information—Cisco NCS 500 Series Routers
Statement 7004—Special Accessories
To comply with emission and immunity requirements, shielded cable is required for connection to Ethernet
Ports.
Statement 7005—Intrabuilding Lightning Surge and AC Power
Fault
Warning
The intrabuilding port(s) of the equipment or subassembly must not be metallically connected to interfaces that
connect to the OSP or its wiring. These interfaces are designed for use as intrabuilding interfaces only (Type 2 or
Type 4 ports as described in GR-1089-CORE) and require isolation from the exposed OSP cabling. The addition of
Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring.
Statement 7012—Equipment Interfacing with AC Power Ports
This equipment shall be connected to AC mains provided with a surge protective device (SPD) at the service
equipment complying with NFPA 70, the National Electrical Code (NEC).
Statement 7013—Equipment Bonding Networks CBN
This equipment is suitable for installations utilizing the insert Common Bonding Network (CBN).
Note
Statement 7016—Battery Return Conductor
The battery return conductor of this equipment shall be treated as DC Isolated (DC-I).
All manuals and user guides at all-guides.com
Regulatory Compliance and Safety Information—Cisco NCS 500 Series Routers
15

Publicidad

Tabla de contenido
loading

Tabla de contenido