• Prot
Pro
Prot
Display
0
SP, In2, alarms, OuP, INF
1
SP, In2, alarms, OuP, INF
2
SP, In2, OuP, INF
+ 4
to disable InP, Out
+ 8
to disable CFG, Ser,
+ 16 to disable SW "power-up - power down"
+ 32 disable manual power latching
+ 64 to disable manual power modification
+128 enables full configuration
Hrd
Hardware configuration
hd. 1
Enable multiset
instrument control
by serial
(tr
Control type
Protection code
Modification
SP, alarms
SP
• Hrd
Val
Multiset
Reversed Instrument
(2 SP)
LED
control by
state
serial
0
1
x
2
x
3
x
x
4
x
5
x
x
6
x
x
7
x
x
x
Val
Control type
0
P heat
1
P cool
2
P heat / cool
3
PI heat
4
PI cool
5
PI heat / cool
6
PID heat
7
PID cool
8
PID heat / cool
9
ON-OFF heat
10
ON-OFF cool
11
ON-OFF heat / cool
12
PID heat + ON-OFF cool
13
ON-OFF heat + PID cool
14
PID heat + cool with relative gain
(see C.MEd parameter)
Selection of derivative action sampling time:
+ 0 sample 1 sec.
+ 16 sample 4 sec.
+ 32 sample 8 sec.
+ 64 sample 240 msec.
Note: LbA alarm is not enabled with
ON/OFF type control
26