al. n
Select number of
enabled alarms
bvt.
Function of M/A
keys
dig.
Function
of digital input
dsp
Defining SV
display function
ld. 1
Val.
Function
0
none
1
MAN/AUTO controller
ld. 2
2
LOC / REM
3
HOLD
4
self-tuning enabled
5
autotuning enabled
6
IN1 repetition
ld. 3
7
enable serial dialogue
8
Error present
9
Softstart running
10
SP1...SP2 Indication
+ 16 LED flashes if active
AL.nr
Alarm 1
Alarm 2
Alarm 3
0
disabled
disabled
disabled
1
enabled
disabled
disabled
2
disabled
enabled
disabled
3
enabled
enabled
disabled
4
disabled
disabled
enabled
5
enabled
disabled
enabled
6
disabled
enabled
enabled
7
enabled
enabled
enabled
+ 8 to enable HB alarm
+ 16 to enable LBA alarm
b u t t
0
No function (key disenabled)
1
MAN / AUTO controller
2
LOC / REM
3
HOLD
4
Alarms memory reset
5
SP1 / SP2 Selection
6
Start / Stop selftuning
7
Start / Stop autotuning
8
Set / Reset outputs Out 1... Out 4
+ 16 disable function in configuration menu
dig.
0
No function (key disenabled)
1
MAN / AUTO controller
2
LOC / REM
3
HOLD
4
Alarms memory reset
5
SP1/SP2 Selection
6
Software on/off
+ 16 for input in denied logic (NPN)
+ 32 to force logic state 0 (OFF)
+ 48 to force logic state 1 (ON)
diSP
Lower display (SV) function
0
SSP - setpoint enabled
1
InP.2 - aux input
2
Control output value
3
Deviation (SSP - PV)
Function of LEDs
27

Publicidad

Tabla de contenido
loading