Fronius Galvo
Adjustment range for grid
voltage
Voltage trip limit accuracy
Setting range for voltage limit vi-
olation tolerance time
Nominal output current
Phases
Maximum continuous utility
backfeed current
Synchronization in-rush current
3)
Max. output fault current per
duration
Nominal output frequency
Operating frequency range
Adjustment range for mains fre-
quency
Frequency trip limit accuracy
Setting range for frequency limit
violation tolerance time
Total harmonic distortion
Power factor (cos phi)
General data
Maximum efficiency
CEC efficiency
Self-consumption at night
Self-consumption during opera-
tion
Cooling
Protection class
Dimensions h x w x d
Weight
Shipping dimensions l x h x w
46
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
3)
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
at 208 V
at 220 V
at 240 V
2.5-1 208-240
3.1-1 208-240
104–288 V
104–288 V
104–288 V
1% of nominal value
0.016–21.0 s
12.0 A AC
14.1 A AC
11.4 A AC
14.1 A AC
10.4 A AC
12.9 A AC
2
0 A
36.0 A / 9.4 ms
456 A/1.9 ms
440 A/1.5 ms
488 A/1.4 ms
60 Hz
45.0 - 65.0 Hz
45.0 - 65.0 Hz
0.05 Hz
0.016 - 600 s
< 4%
1
0.85 - 1 ind./cap.
96.0%
95.0%
95.0%
95.0%
95.0%
95.0%
95.5%
0.7 W
0.9 W
0.9 W
8.0 W
Forced-air ventilation
NEMA4X
24.7 x 16.9 x 8.1 in.
628 x 428 x 205 mm
36.05 lbs.
16.35 kg
30.1 x 21.7 x 11.4 in.
770 x 550 x 290 mm
5)
5)
6)