CONTEMPORARY COMMAND OF 2 UPs
B
WARNING: Connect the accessories (ex. radar, selectors, ecc.) in parallel between both the automations.
The setup of the 2 UPs must be done pressing the PROG buttons of both the control panels simultaneously.
ATTENTION: After making the automatic set up, use the LCD PROGRAMMER to set the "F" parameter on Value = 0 for UP 1 and Value = 1 for UP 2.
Two UPs installed on overlapping leaves
Connect terminals:
INT.I 18 (UP1) => INT.I 18 (UP2)
COM 10 (UP1) => COM 10 (UP2)
OPEN 17 (UP1) => OPEN 17 (UP2)
Two UPs installed on rebated leaves
Connect terminals:
INT.I 18 (UP1) => INT.I 18 (UP2)
COM 10 (UP1) => COM 10 (UP2)
OPEN 17 (UP1) => OPEN 17 (UP2)
ACG9478
UP 2
INT.I 18
COM 10
OPEN 17
Setup UP parameters using LCD PROGRAMMER to enable syncronism for 2 UPs, overlapping leaves:
Parameter R3
Parameter X from1 to 9 (second leaf in closure delay)
Parameter J1 (1,5 s. - second leaf opening delay)
ACG9478
UP 2
INT.I 18
COM 10
OPEN 17
Setup UP parameters using LCD PROGRAMMER to enable syncronism for 2 UPs, rebated leaves:
Parameter R 3
Parameter X 0 (no delay for second leaf in closure)
Parameter J 0 (no delay for second leaf in closure)
ACG9478
UP 1
INT.I 18
COM 10
OPEN 17
ACG9478
UP 1
INT.I 18
COM 10
OPEN 17