Wilo EHV G2 Instrucciones De Instalación Y Funcionamiento página 35

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 57
INSTALLATION
5.2.2. Fastening with HAS... / HIS anchor bolts
• These anchors may only be used in reinforced or unreinforced normal concrete with
a strength class of between C20/25 and C50/60 (according to EN 206:2000-12).
• The anchor bolts are only suitable for crack-free concrete. Optionally, anchor bolts are
also available for cracked concrete.
• The foundation for the anchors should be dry.
• Before using the anchor bolts, the strength of the structure must be ascertained in order
to ensure that the reaction forces can be absorbed.
• Take care not to damage the grout cartridge during transport, as otherwise the adhesive
cement will harden.
• Do not use defective or old grout cartridges (see the use-by date).
• Grout cartridges may only be stored between +5 °C and +25 °C. They must be stored
in a cool, dry and dark place.
• Hazard labeling on grout cartridges
Technical data for anchor and fix anchors
Type
HAS-R M8x80/14
HAS-R M12x110/28
HAS-R M16x125/38
HAS-R M16x125/108
HAS-E-R M20x170/48
HAS-E-R M24x210/54
HIS-RN M16x170
W-FA 10/15/85
* Without external hex head
** M16 female thread
Installation and operating instructions Wilo EHV G2 - DN250
CAUTION – irritant substances!
The grout cartridges contain dibenzoyl peroxide. This substance is an irritant!
Note the following information:
• R36/38 – causes eye and skin irritation
• R43 – may cause sensitization by skin contact
• S37/39 – wear suitable protective clothing when working
• S26 – in case of contact with eyes, rinse thoroughly with water and seek
medical advice
• S28 – after contact with skin, wash immediately with water and plenty
of soap
Rod
Drill hole
length
depth
110 mm
80 mm
160 mm
110 mm
190 mm
125 mm
260 mm
125 mm
240 mm
170 mm
290 mm
210 mm
170 mm
170 mm
85 mm
70 mm
Minimum
Minimum
Drill hole
distance
foundation
diameter
to edge
thickness
10 mm
100 mm
130 mm
14 mm
135 mm
160 mm
18 mm
155 mm
175 mm
18 mm
155 mm
175 mm
24 mm
210 mm
220 mm
28 mm
260 mm
260 mm
28 mm
210 mm
220 mm
10 mm
65 mm
100 mm
English
Maximum
Tightening
component
torque
thickness
10 Nm
14 mm
40 Nm
28 mm
80 Nm
38 mm
80 Nm
108 mm
150 Nm
48 mm*
200 Nm
54 mm*
80 Nm
**
30 Nm
10 mm
35

Publicidad

Tabla de contenido
loading

Tabla de contenido