• InFo Display

Information
INFO
display
8
Serial
(ode
communication
code
9
updt
Software
version
10
ProG
Program number
222
len
Number of
program steps
223
p. t y
Program type and
restart mode
224
Program type and restart mode
0
Restart from first step; the setpoint
copies the value of PV
1
Restart from conditions prior to stop
2
Restart with step search
(see "Programmer Functions")
+ 8 Wait for STOP / START switching
+ 16 Continuous loop; at end of cycle the program restarts
from first step (excludes +32 function)
+ 32 At end of cycle the control output goes to "FAcP"
value, set in "CFG" menu
+64 Fast simulation (see "Programmer Functions")
Selects program and step
StEP
to set
226
SP. s
S step setpoint
227
"S" step ramp time (time set
rp. t
refers to time base selected
[HH:MM or MM:SS] - see
"SP.Pr" parameter in
228
"Hrd" menu)
So. t
"S" step hold time (time set
refers to time base selected
[HH:MM or MM:SS)
229
St. y
Defines "S" step type. Hold Back Band (HBB)
function; lets you disable HBB during a segment or
entire step. Parameter is ON if HBB is enabled
230
(see "SP.Pr" parameter on "Hrd" menu)
Sty
HBB enabled
for ramp
0
1
x
2
3
x
4
5
x
6
7
x
+ 8 to enable slave setpoint ramp
Sl. s
Setpoint slaved to step "S", for
second external channel (to be
retransmitted to a slave
231
controller); available if enabled
(see "SP.Pr" parameter on
"Hrd" menu)
Software
prot
protection
code
11
er. n r
Self diagnostic
error code
12
0
No Error
1
Lo
2
Hi
3
ERR
4
SBR
• ProG
0 ... 3
1 ... 8
0 ... 127
• StEP
P0-0 ... P3-7
Lo_L ... Hi_L
0.0 ... 99.59
0.0 ... 99.59
HBB enabled
HBB referred to PV
for hold
or auxiliary input
PV
PV
x
PV
x
PV
aux. input
aux. input
x
aux. input
x
aux. input
0.0 ... 100.0%
retransmitted
output value
eu. r
"S" step ramp
events
232
eu. s
"S" step hold
events
233
ipt
Step "S" advanced through digital input function. When
digital inputs have state set in this function, program
automatically advances to next step, otherwise it "waits" at
234
end of previous step (function is enabled through "SP.Pr"
parameter on "Hrd" menu); "d.i.F.1" and/or "d.i.F.2" set to 12.
xbb
Hold Back Band value, symmetrical to active
setpoint. Available if enabled (see "SP.Pr"
parameter on "Hrd" menu); can be disabled during
235
a program segment ( see "Sty" parameter).
GrP.
Selection of a control
parameter group during
ramp phases and
242
holding of setpoint
programmer.
+ 16 to force the power limit of group 0 when in "hold" phase
Selection of a control
C.GrP
parameter group
to be set.
243
Proportional band for
h pb
heating or hysteresis for
-
ON/OFF control
244
h it
Integral time
-
for heating
245
h dt
Derivative time
-
for heating
246
h. P . x i
Maximum power limit
for heating
247
Minimum power limit for
h. P . L o
heating (not available for
double heat/cool action)
248
21
Eu.r
or
Event 1
Event 2
Event 3
Eu.S
0
OFF
OFF
OFF
1
ON
OFF
OFF
2
OFF
ON
OFF
3
ON
ON
OFF
4
OFF
OFF
ON
5
ON
OFF
ON
6
OFF
ON
ON
7
ON
ON
ON
8
OFF
OFF
OFF
9
ON
OFF
OFF
10
OFF
ON
OFF
11
ON
ON
OFF
12
OFF
OFF
ON
13
ON
OFF
ON
14
OFF
ON
ON
15
ON
ON
ON
IPt
IN1 = ON
IN2 = ON
0
1
x
2
x
3
x
x
GrP.
Ramp
group
0
0
1
0
2
0
3
0
4
1
5
1
6
1
7
1
8
2
9
2
10
2
11
2
12
3
13
3
14
3
15
3
• C.GrP
0 ... 3
0.0 ... 999.9%
full scale
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
0.0 ... 100.0%
Event 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
0 ... 999
scale points
Hold
group
0
1
2
3
0
1
2
3
0
1
2
3
0
1
2
3