Problem
The unit tends to shut down
GB
The unit is not delivering power
The power supplied is not
constant
TABLE OF ALARM SIGNALS
If the problem or malfunction encountered
is not listed in the table, you should check
Alarm
LOW BATTERY
OIL CHANGE
NO FUEL
OIL TEMP PRESS
GENERATOR ALERT!
OVERLOAD!
SHORT CIRCUIT
OVER TEMPERATURE
LOW POWER ENGINE
All manuals and user guides at all-guides.com
Cause
Oil level too high
Sea water pump rotor worn
Excessive electrical power demand
The power cables are
disconnected or they do not
provide a continuous supply
The inverter is broken
The inverter is broken
Malfunction in the pump power
supply
The power cables are
disconnected or they do not
provide a continuous supply
Injectors dirty or faulty
Air filter blocked
Cooling air/water pipe blocked
Excessive electrical power demand
Cause
Battery low
Indicates that it is necessary to
change the engine oil
Fuel level too low
Insufficient oil in engine
Exhaust gas temperature too high
General alarm
Excessive electrical power demand
Output cable short-ircuit
Inverter overheating
Engine revs too low
-
32
Remedy
Check the oil level, and remove
excess oil if necessary (see "Check
oil level")
Replace the rotor (see "Changing
the water pump rotor")
Decrease the required voltage load
Contact the service department
Contact the service department
Contact the service department
Contact the service department
Contact the service department
Contact the service department
Clean the air filter
Check the cooling air/water pipe
and clean it if necessary
Decrease the required voltage load
the "Alarm signals" table given below.
Remedy
Change the battery
Change the engine oil (see "Changing
engine oil")
Important
On restarting the unit, keep the start switch
pressed for a long time to reset the hour
counter.
Fill up with fuel
Top up with oil of the same type
Check the cooling air/water pipe and
clean it if necessary
See "Finding malfunctions"
Important
If the problem persists, contact the
service department.
Decrease the required load
Eliminate the short-circuit
Switch the appliance off and leave it to
cool.
Decrease the required load
-
User Manual