Alarm codes

32
Commissioning
NOTICE
The priming process lasts no longer than 5 minutes. At the end of each minute,
Wilo-Isar BOOST5 stops the electric pump automatically for 5 seconds, then restarts
it. And so on until Wilo-Isar BOOST5 is primed. During this process, the LEDs will
continue to flash. The priming stage may be brought to a close by timeout
(5 minutes) or the end of the priming stage. The LEDs will stop flashing. If the pump
does not prime itself, repeat the operation.
Flashing green LED + flashing red LED
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Example
Continuous green LED + flashing red LED
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Example
Low water. Starts after 7 seconds of no
water at the suction side. Check for water
at the suction side and fill the pump.
Wilo-Isar BOOST5 attempts automatic re-
start after 1 min, 15 min, 30 min, 1 h, etc.
The pump does not reach the set pres-
sure. Contact customer service.
The tank's preload pressure is too low; in-
flate the tank to 50 % of working pres-
sure (for instance, if working pressure is
3 bar, inflate the tank to 1.5 bar).
Discharge pressure below 0.2 bar (broken
pipe). Reset possible in manual mode only.
Check why the pressure was reset to zero.
Supply voltage too low. Ensure 230 V
±10 % of power supply.
OFF signal from exterior.
Pump in alarm state due to low water
LED 1 flashing + red LED flashing = low
water
Short-circuit. Turn off the device and
contact customer service. Reset possible
in manual mode only.
Excess current. The current absorbed ex-
ceeds the authorised tolerance. Reset
possible in manual mode only. Contact
customer service if the problem persists.
Excessive module temperature. Check the
temperature of the fluid being pumped. If
the fluid temperature is not above 40 °C,
contact customer service. Automatic re-
set if the temperature falls below the
alarm level.
Excessive motor temperature. Check the
temperature of the fluid being pumped. If
the fluid temperature is not above 40 °C,
contact a support centre. Automatic reset
if the temperature falls below the alarm
level.
Invalid pressure sensor signal. Contact
customer service.
Invalid volume flow sensor signal. Contact
customer service.
Pump in alarm state due to short-circuit
LED 1 continuous + flashing red LED =
short-circuit
WILO SE 07/2022